32
Document # 50049 Rev D 5/2/97 P/N 50049:D
Address
Description
Setting
1
Sensor Number
69 - 71
Primary # General Alarm Code
110
000
2
72 - 74
Primary # Zone/Point Alarm Code
110
4
Note
3
75 - 77
Primary # General Supervisory Code
200
000
2
78 - 80
Primary # Zone/Point Supervisory Code
200
Note
3
81 - 83
Primary # General Fault Code
300
84 - 86
Primary # AC Fault Code
301
87 - 89
Primary # Zone/Point Fault Code
380
Note
3
90 - 92
Primary # Low Battery Fault Code
302
93 - 95
Primary # Telco Primary Line Fault Code
351
96 - 98
Primary # Telco Secondary Line Fault Code
352
99 - 101
Primary # NAC Fault Code
321
102 - 104
Primary # Comm. Trouble Primary # Code
354
105 - 107
Primary # Comm. Trouble Secondary # Code
354
108 - 110
Primary # 485 Comm. Trouble Code
300
111 - 113
Primary # System Off Normal Code
308
114 - 116
Primary # UDACT-F Off Normal Code
350
117 - 119
Primary# System 24 Hour Test
602
120 - 122
Primary # System 24 Hour Test w/active event
608
123 - 125
Primary # Manual Test Message
601
Notes:
1) Note: Zero entries prevent the transmission of the report to the Central Station.
2) Refer to Contact ID program locations 64 - 68.
3) The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is
added to the main event code. See Appendix A-3 for more information.
4) Factory default for this report is 110 (110 is transmitted for modules, however, 111 will
automatically be transmitted for smoke detectors). Use Type Mode (refer to Section 4.2) to change
this report per zone or point.
Ademco Contact ID Format
If 'E' is entered for address 16, the following data is automatically programmed for the Primary
phone number event codes.
Enter a '000' for the data setting to disable the report.
Table 3-4: Ademco Contact ID, Primary Number