29
Document # 50049 Rev D 5/2/97 P/N 50049:D
Host Panel ID (63)
Enter one of the following digits corresponding to the Control Panel in which the
UDACT-F is installed. A correct entry is essential for proper operation.
Loop Number (64 - 65)
For Contact ID format only. Factory default is '00'. See Appendix A.
Sensor Number (66 - 68)
For Contact ID format only. Factory default is '000'. See Appendix A.
Programming Event Codes (69-208)
The type of reports and 'event codes' that are sent to the Central Station are in Tables
3-2 through 3-7. The selections made for the Primary Central Station Number
Communication Format (address 16) and the Secondary Central Station Number
Communication Format (address 42) automatically program addresses 69-208 with
factory default selections.
Any of the event codes may be changed. Consult your Central Station prior to
altering the event codes. For the 3+1, 4+1 and 4+1 Express formats entering an
event code of '0' will cause the communicator to NOT transmit the report. Enter two
zeroes for 4+2 and 4+2 Express Formats. For Ademco Contact ID format enter three
zeroes. Transmission of reports to either or both Central Station phone numbers
may be disabled.
Note the special 'System Abnormal Test Report' event code. This report was added
per new UL DACT requirements. This report is generated in place of the normal test
report when an alarm and/or trouble condition exists at the time the test report is
due to be sent.
Programming the Real-Time Clock
Entering an address greater than 209 will cause a display of the current time. On
initial power up, the clock will start running from the factory setting of 00:01
(military time). The far left digit will be flashing, indicating that this is the first digit
to be programmed.
Hours and Minutes, Year, Month and Day
To set the hour, select a digit then press [ENTER/STORE]. The digit 2nd from the
left will start flashing. Select a digit then press [ENTER/STORE]. Hours setting is
complete. With the digit 2nd from the right flashing, select a digit then press
[ENTER/STORE]. The digit on the far right will start flashing. Select a digit then
press [ENTER/STORE]. Minutes setting is complete. Next, select the year, month
and day in a similar fashion.
End Programming
Exit Programming Mode by pressing MODE, followed by the 4-digit code
corresponding to an alternate mode of operation, then press [ENTER/STORE].
During Program Mode, if no key is pressed within 10 minutes, the UDACT-F will
revert to normal mode.
0 = MS-9200
1 = Do not use
2 = Sensiscan 2000
3 = Do not use
4 = Do not use
5 = Do not use
6 = Do not use
7 = Do not use
8 = Do not use
9 = Do not use