![Fire-Lite Alarms UDACT-F Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/fire-lite-alarms/udact-f/udact-f_installation-operation-and-programming-manual_2291128035.webp)
35
Document # 50049 Rev D 5/2/97 P/N 50049:D
Ademco Contact ID Format
If 'E' is entered for address 42, the following data is automatically programmed for the Secondary
phone number event codes.
Enter a '000' for the data setting to disable the report.
Address
Description
Setting
1
Sensor Number
139 - 141
Secondary # General Alarm Code
110
000
2
142 - 144
Secondary # Zone/Point Alarm Code
110
4
Note
3
145 - 147
Secondary # General Supervisory Code
200
000
2
148 - 150
Secondary # Zone/Point Supervisory Code
200
Note
3
151 - 153
Secondary # General Fault Code
300
154 - 156
Secondary # AC Fault Code
301
157 - 159
Secondary # Zone/Point Fault Code
380
Note
3
160 - 162
Secondary # Low Battery Fault Code
302
163 - 165
Secondary # Telco Primary Line Fault Code
351
166 - 168
Secondary # Telco Secondary Line Fault Code
352
169 - 171
Secondary # NAC Fault Code
321
172 - 174
Secondary # Comm. Trouble Primary # Code
354
175 - 177
Secondary # Comm. Trouble Secondary # Code
354
178 - 180
Secondary # 485 Comm. Trouble Code
300
181 - 183
Secondary # System Off Normal Code
308
184 - 186
Secondary # UDACT-F Off Normal Code
350
187 - 189
Secondary # System 24 Hour Test
602
190 - 192
Secondary # System 24 Hour Test w/active event
608
193 - 195
Secondary # Manual Test Message
601
Notes:
1) Note: Zero entries prevent the transmission of the report to the Central Station.
2) Refer to Contact ID program locations 64 - 68.
3) The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is
added to the main event code. See Appendix A-3 for more information.
4) Factory default for this report is 110 (110 is transmitted for modules, however, 111 will automatically
be transmitted for smoke detectors). Use Type Mode (refer to Section 4.2) to change this report per
zone or point.