Primary Number 24/12 Hour Test Time Interval (25). The test report sent to the
Primary phone number may be sent every 12 or 24 hours. If the message is to be sent
every 24 hours, leave the factory default entry of zero. If 12 hour test report time is
needed, enter 1=12 hours.
Secondary Phone Number (26-41). Programming is similar to programming the
primary phone number located at addresses 00 - 15. The defaults are also all 'F's.
F F F F F F F F F F F F F F F F
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 .
Secondary Number Communication Format (42). Programming is the same as the
primary number's Comm Format at address 16. Default entry is 'A', 4+2 Standard.
Choose one entry from the list below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: Not Used
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: Not Used
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: Not Used
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: Not Used
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: Not Used
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: Not Used
E: Ademco Contact ID
F: Not Used
Secondary Number Account Code (43-46) is programmed in addresses 43 - 46 in
the same manner as the primary phone number Account Code. Default entries are all
'0s'.
Secondary Number 24-Hour Test Time (47-50) is programmed in addresses 47-
50 in the same manner as the primary number 24-Hour Test Time. Default is 00:00
(12:00 midnight).
Secondary Number 24/12 Hour Test Time (51) The test message sent to the
Secondary phone number may be sent every 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of zero. If a 12 hour test report
time is needed, enter 1=12 hours.
Use the Start and End Monitoring Address programming locations to set the
reporting range of the UDACT-F.
Start Monitoring Address (52-53) is programmed to indicate the first group of
zones or points to be monitored and reported to the Central Station. Default is '01'.
Valid entry is '01'. See Table 3-1.
End Monitoring Address (54-55) is programmed to indicate the last group of zones
or points to be monitored and reported to the Central Station. Default is '01'. Valid
entries are '01' and '04'. See Table 3-1.