Document D150-00-155-IS   Issue 2   11-08-2022 

 

 

Sheet 1 of 3 

 

 

 

www.e2s.com  Fax +44 (0)208 740 4200 

 

INSTRUCTION MANUAL 

BExCP3C-PB Push Button Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 

 

BExCP3C-PB 
Manual Call Point – Push Button 
With resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres 

 

1) 

Introduction 

The  BExCP3C-PB  is  a  push  button  manual  call 
point  which  is  certified  to  the  European  and 
International  Gas  and  Dust  standards.  The  unit 
meets  the  requirements  of  the  ATEX  directive 
2014/34/EU and IECEx scheme. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present. 
 
All units have up to two of the following: 

 

Monitoring resistors up to 1.5W per module 

 

Monitoring diode 

 

Monitoring Zener diode 

 
The units are Group II, EPL (equipment protection 
level) Gb. The equipment is certified ‘Ex db eb mb 
IIC  T4  Gb’  and  as  such  may  be  used  in  Zones  1 
and 2 with flammable gases and vapours with gas 
groups  IIA,  IIB  &  IIC  and  temperature  classes  T1, 
T2, T3 and T4. 
These  units  are  also  Group  III,  EPL  Db.  The 
equipment is certified ‘Ex tb IIIC T75ºC Db’ and as 
such  may  be  used  in  Zones  21  and  22  for 
combustible dusts groups IIIA, IIIB & IIIC. 
 

2) 

Ratings & Marking 

All  units  have  a  rating  label,  which  carries  the 
following important information: - 
 
Unit Type No.: 
BExCP3C-PB Manual Call Point  
 
Input Voltages: 

Important: 

See section 7.1 for current ratings 

 

125VDC Max    0.5A Max. Resistive Load;  

       0.03A Max Inductive Load 

75VDC Max      0.75A Max 
48VDC Max      1.0A Max 
24VDC Max      5.0A Max Resistive Load; 

       3.0A Max Inductive Load 

12VDC Max      5.0A Max 
6VDC Max        5.0A Max 
 
Code: 
BExCP3C-PB 

      

Ex db eb mb IIC T4 Gb      
Ex tb IIIC T75ºC Db 

      

IP66 

 

      

–40ºC <= Ta <= +65ºC      
 
Certificate No.: 
SIRA 09ATEX3286X 
IECEx SIR 09.0121X 
CSAE 21UKEX3556X 
 
Epsilon x:                           II 2GD 
 
 
CE Marking 
Notified  

  

2813 

Body No.               
 
UKCA Marking 
Notified Body No.

 

0518 

 
 
Year/Serial No. i.e. 20/1CP3CPB000001 
 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT 

 
3) 

Type Approval Standards 

The  beacon  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards: - 
EN60079-0:2018 / IEC60079-0:2017 
EN60079-1:2014 / IEC60079-1:2014 
EN60079-7:2015 / IEC60079-7:2017 

EN60079-18:2015 / IEC60079-18:2014 
EN60079-31:2014 / IEC60079-31:2013 
 
The equipment is certified for use in ambient 
temperatures in the range  
BExCP3C-PB -40

o

C to +65

o

and shall not be used outside this range. 
 

4) 

Installation Requirements 

Installation  of  this  equipment  shall  only  be  carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g.  
IEC 60079-14/EN 60079-14 

 

Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 
 
Refer  to  certificates  SIRA  09ATEX3286X,  IECEx 
SIR  09.0121X  and  CSAE  21UKEX3556X  for 
special conditions of safe use. 
 
The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

Aluminium  Pressure  Die  Cast  Body 

LM6 
 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
Potting Compound of resistors where used: Epoxy 
Resin 
 
If the equipment is likely to come into contact with 
aggressive substances,  then it is the  responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
“Aggressive  substances”  -  e.g.  acidic  liquids  or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 
 

 

View of base unit showing fixing centres. 
 
To  gain  access  to  the  mounting  holes  in  the  base 
the front cover must be removed.  
This  is  achieved  by  removing  the  4  off  M4  cap 
head bolts holding on the cover. 
 

 

 
Once the screws are removed the cover will hang 
down out of the way to gain access to the Ex e 
terminal block, the internal earth terminal and 
mounting hole recesses.

 

Содержание BExCP3A-PB

Страница 1: ...tion certificate issued by SIRA and have been approved to the following standards EN60079 0 2018 IEC60079 0 2017 EN60079 1 2014 IEC60079 1 2014 EN60079 7 2015 IEC60079 7 2017 EN60079 18 2015 IEC60079 18 2014 EN60079 31 2014 IEC60079 31 2013 The equipment is certified for use in ambient temperatures in the range BExCP3C PB 40o C to 65o C and shall not be used outside this range 4 Installation Requi...

Страница 2: ... is determined as the smallest value from the following scenarios 1 When both module resistor values are the same as or above the minimum range of values shown in table 1 the current is not further limited However when either resistor value is lower than those shown in table 1 the current must be limited to the values given in table 2 Voltage option Max Voltage Max current when resistor values low...

Страница 3: ...are fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure to close a contact when the call point is struck with specified force Failure to open a contact when the call point is struck with specified force Spurious output despite no input Integrity in respect of failure to close SIL 2 Total Failure rate 0 133 pmh hazardous failure rate revealed 0 pmh hazardous failure...

Страница 4: ...A PB BExCP3B PB BExCP3C PB BExCP3D PB BExCP3E PB Acionador Manual de Alarme com Botão Pulsador de Rearme Rotativo por Chave BExCP3A PT BExCP3B PT BExCP3C PT BExCP3D PT BExCP3E PT Certificado Sira 09ATEX3286X e Certificado IECEx SIR 09 0121X O seguinte texto será reproduzido sem alteração no manual de instruções dos produtos acima e um manual de instruções acompanhará cada produto ou lote de produt...

Страница 5: ... mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão Tensão nominal 24V mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão Tensão nominal 24V mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão ...

Страница 6: ... mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão Tensão nominal 24V mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão Tensão nominal 24V mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão ...

Страница 7: ... mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão Tensão nominal 24V mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão Tensão nominal 24V mostrada consulte as observações para obter informações sobre as alterações necessárias para outras variantes de tensão ...

Страница 8: ...mentos são certificados como Ex db eb IIC T6 Gb e como tais podem ser utilizados nas Zonas 1 e 2 com gases e vapores inflamáveis e com os grupos de aparelhos IIA IIB IIC e classes de temperatura T1 T2 T3 T4 T5 e T6 As unidades também são Grupo III e EPL Db Os equipamentos são certificados como Ex tb IIIC T75ºC Db e como tais podem ser utilizados nas Zonas 21 e 22 para os grupos de pós combustíveis...

Страница 9: ... e IIIC Os equipamentos são certificados somente para uso em temperaturas entre 40o C e 65o C e não deverão ser utilizados fora desta faixa Acionador Manual de Alarme Quebra Vidro BExCP3D BG Acionador Manual de Alarme com Botão Pulsador de Rearme BExCP3D PB Acionador Manual de Alarme com Botão Pulsador de Rearme Rotativo por Chave BExCP3D PT Todas as unidades têm até dois resistores de monitoramen...

Страница 10: ...alizado somente por pessoal adequadamente treinado em conformidade com o código de prática aplicável ex IEC 60079 19 EN 60079 19 7 A certificação destes equipamentos se deve a estes materiais utilizados na construção dos mesmos Carcaça Corpo de Alumínio Fundido Resistente à Pressão LM6 Mecanismo interno à carcaça Molde por Injeção de Plástico Nylon Zytel Selagem da carcaça e mecanismo O ring de Bo...

Страница 11: ...L CALL POINT BExCP3B C D PB PUSH BUTTON MANUAL CALL POINT BExCP3B C D PT TOOL RESET MANUAL CALL POINT IS CP4B BG BREAK GLASS MANUAL CALL POINT IS CP4B PB PUSH BUTTON MANUAL CALL POINT IS CP4B PT TOOL RESET MANUAL CALL POINT 1A Circuit shown in Unoperated condition Glass Intact Standby Condition Terminals 2 3 4 5 open Terminals 2 3 6 closed 1B Circuit shown in Operated condition Glass Broken Button...

Страница 12: ...ands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment BExCP3A BExCP3B BExCP3C BExCP3D BExCP3E II 2G Ex db eb IIC T6 Gb 40 C Ta 70 C II 2D Ex tb IIIC T75 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 50 C II 2D Ex tb IIIC T60 C Db 40 C Ta 50 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 65 C II 2D E...

Страница 13: ...ry high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rated IP66 Construction and design requirements according to EN54 11 2001 clause 4 7 BExCP3A BG B BG C BG D BG only fitted with burning house symbol shown in figure 3a and no lift flap On behalf of European Safety Systems Ltd I declare that on the date the equipment ...

Страница 14: ...xCP3A BExCP3B BExCP3C BExCP3D BExCP3E II 2G Ex db eb IIC T6 Gb 40 C Ta 70 C II 2D Ex tb IIIC T75 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 50 C II 2D Ex tb IIIC T60 C Db 40 C Ta 50 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 65 C II 2D Ex tb IIIC T75 C Db 40 C Ta 65 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 70 C II 2D Ex tb IIIC T80 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C ...

Страница 15: ...ed by enclosures IP code enclosure rated IP66 Construction and design requirements according to EN54 11 2001 clause 4 7 BExCP3A BG B BG C BG D BG only fitted with burning house symbol shown in figure 3a and no lift flap On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical ...

Отзывы: