28
Document # 50049 Rev D 5/2/97 P/N 50049:D
Note: For additional information on the starting and ending addresses,
refer to the host FACP Technical Manual.
Table 3-1: Start and End Monitoring Address
UDACT-F Communication Selection (56)
Leaving address 56 at '0' disables communications to the Central Station(s). Enter '1'
for zone reporting, receive only, '2' for zone reporting, receive/transmit, '3' for
consecutive point reporting, receive only, '4' for consecutive point reporting, receive/
transmit, '5' for code wheel matching point reporting, receive only or '6' for code
wheel matching point reporting, receive/transmit. See Type Mode Section 4.2 for
additional information on code wheel match reporting. Note: Use receive only
selections when using remote annunciators. Be certain to set one of the
annunciators for receive/transmit for EIA-485 communications bus supervision. Use
the receive/transmit entries when annunciators are not installed or when the
UDACT-F receive/transmit function is to be used to supervise the EIA-485
communication bus. For additional information on the receive/transmit function,
refer to annunciator technical manuals.
Backup Reporting (57) Leaving address 57 at '0' means that reports will be
transmitted to the secondary phone number only if attempts to communicate to the
primary phone number are unsuccessful. Programming a '1' causes all reports to be
transmitted to the secondary phone number.
Touchtone/Rotary Select (58) A '0' programmed in this address by the factory
triggers Touchtone dialing over both phone lines. Select '1' for rotary dialing.
Make Break Ratio (59) Set this address only if address 58 is set to '1'. Address 59 is
factory set to '0' which is a 67/33 ratio, but may be changed to '1' which is 62/38.
Address (60) Leave default of 0.
Address (61) Leave default of 0.
AC Loss Reporting Delay (62) '1' is factory default which causes a 6 hour time
delay for AC loss reporting. Valid entries are '0' to '9' and 'A' to 'F' corresponding to
the following reporting delay times: '1' = 6 hours; '2' = 7 hours; '3' = 8 hours; '4' = 9
hours; '5' = 10 hours; '6' = 11 hours; '7' = 15 hours; '8' = 16 hours; '9' = 17 hours; 'A'
= 18 hours; 'B' 19 hours; 'C' = 20 hours; 'D' = 21 hours; 'E' = 22 hours; and 'F' = 23
hours. '0' entry causes immediate reporting of AC loss.
Zone Reporting (Factory Default)
Point Reporting
START
Addr. 52-53
END
Addr. 54-55
START
Adtr. 52-53
END
Addr. 54-55
MS-9200
MS-9200
S2000
S2000
1 = Report status of 56 software zones
2 = Report status of 56 zones
1 = Report status of 198 points
01
1
01
1
01
04
1
N/A
01
2
01
N/A
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com