background image

P84025 F 

Sheet 1 of 6 

 

273 Branchport Ave. 
Long Branch, N.J.  07740     
(800)  631-2148 (

USA

)                     

Thank you for using our products.

 

(800)  397-5777 (

CANADA

)                        

INSTALLATION INSTRUCTIONS

 

www.wheelockinc.com 

         

 

 

 

SERIES RSS STROBE APPLIANCES

 

(CEILING MOUNT VERSIONS) 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL

Wheelock’s Series RSS Strobes can provide a non-synchronized strobe signal when connected directly to a Fire Alarm Control Panel 
(FACP), or provide a synchronized strobe signal when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM), or 
Power Supply (PS-12/24-8 

UL Only

).  The Series RSS Strobe Appliances are UL Listed under Standard 1971 (Emergency Devices 

for the Hearing Impaired) for Indoor Fire Protection Service. The Series RSS Strobe Appliances are also ULC Listed under Standard 
CAN/ULC-S526-M87 for Visual Signaling Appliances.  These Strobe models are listed for 

ceiling mount

 

only,

 with the backboxes 

specified in these instructions (See Mounting Options).  RSS models have an integrated Strobe Mounting Plate (SMP) that can be 
mounted to a single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox.  The strobes use a Xenon 
flashtube with solid state circuitry enclosed in a rugged Lexan

 lens to provide maximum visibility and reliability for effective visible 

signaling.  All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP. 

NOTE

:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol  

.  All warnings are printed in bold capital letters. 

 

WARNING:  THE RSS STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT." 

 

NOTE

:  All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - 

CAN/ULC

-S524-01 and Canadian Electrical Code, Part 1.  Final acceptance is subject to Authorities Having Jurisdiction. 

 

WARNING:  READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 

 

Table 1:  Ratings Per UL and ULC

 

Model 

 

Regulated 

Voltage 

VDC/VRMS 

Voltage 

Range Limit Per UL 1971 

VDC/VRMS 

Voltage Range Per 

CAN/ULC-S526-M87 

VDC/VRMS 

Strobe 

Candela 

(CD) 

Mounting 

Options 

RSS-2415C 24 

16.0-33.0 

20.0-31.0 15 

A,B,C,D 

RSS-2430C 24 

16.0-33.0 

20.0-31.0 30 

A,B,C,D 

RSS-2475C 24 

16.0-33.0 

20.0-31.0 75 

A,B,C,D 

RSS-24100C 24 

16.0-33.0 

20.0-31.0 100 

A,B,C,D 

RSS-2415CR 24 

16.0-33.0 

20.0-31.0 15 

A,B,C,D 

RSS-2430CR 24 

16.0-33.0 

20.0-31.0 30 

A,B,C,D 

RSS-2475CR 24 

16.0-33.0 

20.0-31.0 75 

A,B,C,D 

RSS-24100CR 24 

16.0-33.0 

20.0-31.0 100 

A,B,C,D 

 

NOTES

1.  Strobes will produce 1 flash per second over the “Regulated Voltage” range. 
2.  All models are UL Listed for indoor use with a temperature range of +32oF  to +120oF  (0oC to +49oC) and maximum humidity 

of 93% RH, 

±

2%. 

 

NOTE:  THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.  THE MAXIMUM NUMBER 
OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47. 

 

WARNING:  FOR UL APPLIACATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 

16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR).  DO NOT APPLY 80% AND 110% OF 
THESE VOLTAGE VALUES FOR SYSTEM OPERATION. 

 

WARNING:  FOR ULC APPLIACATIONS THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 

20-31 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR).  APPLY 80% AND 110% OF THESE 
VOLTAGE VALUES FOR SYSTEM OPERATION. 

 

Copyright 2002 Wheelock, Inc.  All rights reserved. 

Содержание RSS-2415C

Страница 1: ...ndard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is subject to Authorities Having Jurisdiction WARNING READ THESE INSTRUCTIONS CAREFULLY FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHIC...

Страница 2: ... AVERAGE CURRENT TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM S PRIMARY AND SECONDARY POWER SOURCES NAC CIRCUITS SM DSM SYNC MODULES OR PS 12 24 8 POWER SUPPLY DO NOT EXCEED THE POWER SOURCES RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RA...

Страница 3: ... 85 3 8 7 7 5 14 18 8 27 25 0 41 90 3 8 6 7 5 13 18 8 26 25 0 36 Table 3A Vertical Plane Vertical 15C CR 30C CR 75C CR 100C CR Angle in deg UL Min Typ 15C UL Min Typ 30C UL Min Typ 75C UL Min Typ 100C 0 15 0 21 30 0 42 75 0 90 100 0 132 5 13 5 21 27 0 42 67 5 88 90 0 129 10 13 5 21 27 0 42 67 5 87 90 0 127 15 13 5 20 27 0 40 67 5 83 90 0 121 20 13 5 19 27 0 38 67 5 79 90 0 116 25 13 5 19 27 0 38 6...

Страница 4: ...box to accommodate the field wires and stresses from the wires could damage the product Although the limits shown for each mounting option comply with the National Electrical Code NEC Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires whenever possible to provide additional wiring room for easy installation and minimum stress on the product fro...

Страница 5: ...ROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS WARNING A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTANCES MIGHT INDUCE A PHOTO SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE TO MINIMIZE THIS POSSIBLE HAZARD WHEELOCK STRONGLY RECOMMEN...

Страница 6: ...ED RESULTS THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION IMPROPER SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORM...

Отзывы: