background image

3 | Installation

2.1 | Access the address switches

1 | Overview

Caution!

Remove all power (AC and battery) before making any 

connections. Failure to do so might result in personal 

injury and/or equipment damage.

5 | Status indicators

Status 

indicator

Function

Ready to turn on (arm)

Turned on (armed)

GAS

Gas alarm

AC (Mains) power present

Fire keypad 

indicator

Function

Fire alarm

Silenced

Supervisory condition

System trouble

Adjusting nightlight (for control panels with version 2.01 or 

higher):

1.  Press [MENU] or press [CMD][8] to open the Main menu.

2.  Use [NEXT] to go to the Press 5 for Settings Menu option, 

or simply press [5].

3.  Use [NEXT] to go to the Press 4 for Keypad Config

 

option, 

or simply press [4].

4.  Use [NEXT] to go to the Press 4 for Nightlight

 

option, or 

simply press [4].

5.  Use [PREV] or [NEXT] to toggle between the Yes and No 

options.

6.  Press [ENTER] while viewing the desired option to save the 

programming.

7.  Press [ESC] to exit the menu.

Adjusting the brightness:

1.  Press [MENU] or press [CMD][8] to open the Main menu.

2.  Use [NEXT] to go to the Press 5 for Settings Menu option, 

or simply press [5].

3.  Use [NEXT] to go to the Press 4 for Keypad Config

 

option, 

or simply press [4].

4.  Press [1] to adjust the brightness.

5.  Use [PREV] or [NEXT] to adjust the brightness level. The 

changes apply immediately.

6.  Press [ESC] to exit the menu.

4 | Display

3.1 | Install the keypad

3.2 | Attaching to the control panel

You can surface install the keypad, or install it to standard 

electrical boxes, including single gang boxes.

1.  Use the base as a template to mark surface.

2.  Pull the wiring through the opening in the base.
3.  Use the mounting hardware to attach.

Use the control panel terminals labeled R, Y, G, B (PWR, A, B, 

COM). Connect them to the keypad terminals labeled R, Y, G, B.

Keypads can be wired directly to the control panel or from 

keypad to keypad.

Callout ― Description

1 ― Control panel
2 ― Terminal wiring
3 ― Keypad’s wiring terminal block

1

2

3

R

Y

G

B

SDI2

PWR+/R

A/Y

B/G

COM/B

27

28

29

26

SDI2

PWR+/R

A/Y

B/G

COM/B

28

29

30

27

Reconnect the keypad to the base by sliding the keypad onto 

the base (reverse of 

Step 2

). Apply power to the system.

SDI2

PWR+/R

A/Y

B/G

COM/B

27

28

29

26

SDI2

PWR+/R

A/Y

B/G

COM/B

28

29

30

27

R

Y

G

B

2 | SDI2 address switches

Two switches set the address for the keypad. The control panel 
uses the address for communication. 

GAS

GAS

Set the address switches per the control panel configuration. 

Each SDI2 keypad must have a unique address. For single-

digit addresses 1 through 9, set the tens switch to 0. The 

following illustration shows the address switch setting for 

address 1.

Callout ― Description

1 ― Address switches

1

2.2 | Setting the address switches

1.  Use a slotted screwdriver. Turn the lock counter-

clockwise.

2.  Push down on the keypad to remove it from the base.

3.  Find the switches on the back of the keypad.
Refer to the following illustrations.

1

2

This keypad is an SDI2 bus compatible 

Callout ― Description

1 ― Wall mount holes
2 ― Single gang box holes
3 ― Double gang box holes
4 ― Wire opening
5 ― Surface mount wire openings
6 ― Gang box holes (3-4 in)
7 ― Surface mount wire channel
8 ― Bubble level
9 ― SDI2 wiring terminal block
10 ― Wire tie posts

R  Y  G  B

6

2

4

9

1

2

3

3

7

7

5

5

1

1

10

6

6

5

8

10

10