Page 70 of 91
Rev. 4.20
15.1.3
Smoke detector
The smoke detector reacts to the presence of elements caused by the combustion (visible smoke). The working
principle is based on the light dispersion technique (Tyndall effect).
ADDRESS
:
the point and loop addresses (no mod.).
ZONE
:
the zone address of the point loop (mod., range value
1-63
).
NAME
:
the name of the point (mod.).
TYPE
:
point type (no mod.).
SECTION
:
the section where the point is (no mod.).
O.OF SERVICE
:
it indicates if the point is in out of service (mod.
YES
or
NO
).
FAULT
:
it indicates if the point is fault (no mod.).
LED ON
:
if
YES
the leds flash (mod.
YES
or
NO
).
INPUT
:
the input is activable like only
TECHNOLOGICAL
type
(mod.).
SING.CONSEN.
:
it is used when the control panel is supervisory mode
and the zone of the point is enabled the "double
consent". If
YES
, when the detector go to alarm status,
the control panel go to fire alarm too. The possibility to
modify this function is given provided that there are at
least 2 points on the specific zone. If after deleting of a
point, the assigned zone at single consent has only
one installed point, this parameter value will read
No
(mod.
YES
or
NO
).
SERIAL NUM
:
the serial number of the detector (no mod.).
SW VERSION
:
the software version of the detector (it is changed
through PC).
SUP.SMOK LEV
:
the smoke level in supervisory mode. This level refers
at the
SMOKE
value (mod. Range:
80-150
). Beyond
this value, the alarm goes active.
NSUP.SMK LEV
:
the smoke level in no supervisory mode. This level
refers at the
SMOKE
value (mod. Range:
80-150
).
Beyond this value, the alarm goes active.
SMOKE(0-255)
:
it indicates the smoke into the detector with a range of
0-255
(no mod.).
DIRTY %
:
the dirty % of the detector. If the value exceeds
80%
,
the control panel send the problem with a message
(no mod.).
EFFICIENCY %
:
the efficiency % of the detector. If the value goes
under
25%
, the control panel send the problem with a
message. This value depends of the device sensor (no
mod.).
Point setting
•ADDRESS: 001-1
ZONE: 01
NAME: ROOM1
TYPE: SMOKE DETECTO
SECTION: A-B
OUT OF SERVICE: NO
FAULT:
NO
LED ON: NO
INPUT: DISABLED
SINGLE CONSENSE: NO
SERIAL NUM:002-00001
SW VERSION: 2.00
SUPERV.SMOK LEV: 130
NSUPER.SMOK LEV: 100
SMOKE (0-255): 003
DIRTY %: 000
EFFICIENCY %: 100
Esc. Pre. Next Mod.