Page 46 of 91
Rev. 4.20
9.1.4 Output setting
Inside a the “
Output setting
” menu it is possible to modify the output
parameters (for example in this picture there is a input/output module).
To modify the data use the arrows to move inside the control panel/loop and
modify with “
Mod.
” key if it is allowed.
The output display presents the disabled status of the input/output module
(for example).
If there are not any items, it is because those items are not available.
OUTPUT ADDRESS
: it indicates the address and the loop of the output (no
mod.).
TYPE
:
it indicates the output type: “
24 Vdc
”, “
SIREN
”,
“
FAULT
”, “
CONTR.PANEL OUT.
” and “
LOOP OUTPUT
”
(no mod.).
DEVICE
:
output device type (no mod.):
“
PWR SUPPLY.
”: fixed output of power supply;
“
SUPERV.RELAY
”: supervisory relay output;
“
RELAY
”: no supervisory relay output;
“
OPEN COLL.
”: open collector output.
OUT OF SERVICE
: it indicates if the output is in out of service (mod.
YES
or
NO
).
FAULT
:
it indicates if the output is fault (no mod.).
TEST RUN
:
it permits to run a output activation test (mod.:
YES
or
NO
).
ACTIVATION
:
it permits to activate the output (mod.):
“
NO
”: the output is not enabled;
“
STATUS
”: the output is enabled if anybody conditions
are true; it is possible to set some formulas for this
modality (
OR-OR, OR-AND, AND-AND
);
“
ZONE REPETITION
”: the output is activated if a zone
of a loop goes to fire alarm;
“
FORMULA
”: no available.
SILENT MODE
:
it sets up the possibility to manual silence the output,
without that the user must do the fire restoration
operation (mod.):
“
NO
”: the silent mode is possible to do only from “fire
restoration”;
“
SINGLE
”: in this command mode it is possible to
independently silence the output. To execute this
function, make reference to the chapter reported -
4.5.2;
“
GLOBAL
”: the user can silence the output through
“
OUT.GLOBAL SILENCING
” in the evacuation menu
(see
13.2);
ACTIV. DELAY s
: it sets up the activation delay. If it is not set up, the
delay is null (mod. range:
000-600
).
MAN.ALARM ACTIV:
visible only if “
ACTIV. DELAY
” is not 0, it permits to
set up the output immediately activation in manual
alarm case from a push button. Normally this function
is disabled (mod.:
YES
or
NO
).
OUT ACTI.TIME s
: it sets up the activation duration. If it is not set up, the
duration is unlimited until at restoration (mod. range:
000-600
).
INVERT
:
it permits to invert the output function (mod.:
YES
or
NO
).
Output setting
OUTPUT ADDRESS:001-1
TYPE: LOOP OUTPUT
DEVICE: RELAY
OUT OF SERVICE: NO
FAULT: NO
STATUS: DISABLED
TEST RUN:
NO
•ACTIVATION:
NO
SILENT MODE: NO
ACTIV. DELAY s: -
MAN.ALARM ACTIV:
NO
OUT ACTI.TIME s: -
INVERT: NO
Esc. Pre. Next Mod.