Page 30 of 91
Rev. 4.20
The same procedure can be repeated for the points with address=0, assigning and acknowledgement for new
starting addresses.
Example: on the first floor of a building the addresses are from 10 to 20 for detectors, from 80 to 84 for buttons,
from 100 to 104 for input/output modules are assigned;
on the second floor the addresses from 21 to 40 for detectors, from 85 to 87 for buttons, from 105 to 109 for
input/output modules are assigned; etc.
Reserve the addresses from 10 to 60 for detectors.
Reserve the addresses from 80 to 90 for buttons.
Reserve the addresses superior to 100 for input/output modules.
FLOORS
DETECTORS
BUTTONS
I/O MODULES
First floor
10-20
80-84
100-104
Second floor
21-40
85-87
105-109
Third floor
45-58
88-90
110-118
PRE-ADDRESSED FURTHER ACQUISITION POINTS
Procedure to be executed to get formerly installed and pre-addressed further points
along a loop.
Enter “
Main menu
”,
à
“
POINT
”,
à
“
insert
”
à
“
AUTOMATIC INCREASE
”,
à
“
PRESET ADDRESS
”
à
“
LOOP
”. The first free address to get is proposed.
However it is possible to insert a different number of address to get if available.
Check the sensor control values and give “
Ok
”.
The control panel will get the points in succession confirming the occurred
identification with a beep. In case of missing points, these will not be acquired; the
control panel will continue to search for the missing point till the “time out” period
ends, then it will pass to the next address the procedure can be interrupted when the
writing “
Canc
” is present.
INSTALLATION OF UNADDRESSED FURTHER DETECTORS
Procedure to be executed to insert un-addressed further detectors, on a formerly
installed base, along a formerly active loop and that presents addressed points (no
points with address zero).
Enter “
Main menu
”,
à
“
POINT
”,
à
“
insert
”
à
“
AUTOMATIC INCREASE
”,
à
“
INSTALLATION
”,
à
“
LOOP
”. Select the first programmable address.
However it is possible to insert a different number of address to assign to the point if
available.
Check the detector control values and give “
Ok
”.
Install a point at a time
and check the sequence of flashes that show the acquired
address.
The control panel gives a beep for each acquired point.
To finish the installation, push “
Canc
”. Wait for the end of the “
SECTION
CALCULATING
”. The message “
COMPLETED OPERATION
” will appear on the display.
Case where there is the
preaddressed point
.
Warning: if a point with
address like a formerly
installed point on the loop
is installed, a fault for loop
overload will be produced.
No point with address=0
must be installed on the
loop.
The point to add must
have address zero.
A point at a time must be
inserted.