Page 8 of 91
Rev. 4.20
1.2 POINT ADDRESSING AND ACQUISITION
The necessity of being able more and more to facilitate the phase of starter of the system from part of the
installer, has made way of having to develop more ways of installation of the points in the loop. The installer turns
out therefore not obliged from procedures rigid and standards, being able to choose at second of the situations
the way simpler than installation.
The acquisition of a point from the control panel, can be executed with four different procedures of acquisition
addressing:
1.
Acquisition for
installation
(valid only detectors);
2.
Acquisition for
activation
;
3.
Acquisition for
serial number
(only if the serial number label is present in the point);
4.
Acquisition for
preset address
.
For a suitable selection of the acquisition procedure, refer to the “PRELIMINARY REMARKS FOR A CORRECT
INSTALLATION”.
Remember that:
The acquisition of points through the installation is preferred when it is necessary to insert further un-addressed
detectors on the loop, but on already installed base, along and already active loop and that presents already
addressed points (example: isolators modules – buttons).
The acquisition of points through starting provides for the activation of already installed points along the loop. Such
points must have address 0.
The acquisition of points through serial number provides for the acquisition of a point through the research of the
series number of the same point.
The acquisition of points through the preset address provides for the acquisition of further already installed points on
the loop and addressed previously. The user must not have points with address 0 on the loop.
For more information see chapters:
7.1 and
0.