Page 69 of 91
Rev. 4.20
15.1 DETECTORS
All detectors of the
EXCELLENT FIRE SYSTEM
series
(smoke, heat and multi-criterion) have the same base.
These detectors have a double led indicator at high
visibility (360°) and a low height.
From the control panel is possible to change the
settings, values, zones and alarm types.
CLIPS DESCRIPTION OF THE BASE
2
3
1
6
5
4
Reed
1
2 / R
Negative output for outside door repeater.
3 / R
4 / SCR.
5 / -
- LOOP.
6 / +
+ LOOP.
15.1.1
Detector addressing
For the addressing it is necessary to use a magnet near the reed. For the procedures refer to the manual of the
control panel.
15.1.2
Manual zero setting of the address
Normally the factory address is equal to 0 (zero). If the user must take back manually the address to such a value,
it is necessary to supply the detector at 24Vdc and, after about ten seconds, approach reed a magnet and wait
the leds make a longer flash signal.
PART 15
POINTS DESCRIPTION AND UTILIZATION