Page 72 of 91
Rev. 4.20
15.1.5
Multicriterion detector
The smoke/heat multi-criterion detector reacts to the presence of products caused by the combustion (visible
smokes) as regards the smoke. The working principle is based on the light dispersion technique (Tyndall effect).
For the detection of the heat, it has been designed to activate itself when the heat exceeds a certain previously
fixed level or when the speed with which this increment is produced is high, even though the programmed level
has not been exceeded.
ADDRESS
:
the point and loop addresses (no mod.).
ZONE
:
the zone address of the point loop (mod., range value
1-
63
).
NAME
:
the name of the point (mod.).
TYPE
:
point type (no mod.).
SECTION
:
the section where the point is (no mod.).
O.OF SERVICE
:
it indicates if the point is in out of service (mod.
YES
or
NO
).
FAULT
:
it indicates if the point is fault (no mod.).
LED ON
:
if
YES
the leds flash (mod.
YES
or
NO
).
INPUT
:
the input is activeable like only
TECHNOLOGICAL
type
(mod.).
SING.CONSEN.
:
it is used when the control panel is supervisory mode and
the zone of the point is enabled the "double consent". If
YES
, when the detector go to alarm status, the control
panel go to fire alarm too. The possibility to modify this
function is given provided that there are at least 2 points
on the specific zone. If after deleting of a point, the
assigned zone at double consent has only one installed
point, this parameter value will read
No
(mod.
YES
or
NO
)
and the zone must be at single consent.
SERIAL NUM
:
the serial number of the detector (no mod.).
SW VERSION
:
the software version of the detector (it is changed through
PC).
SUP.SMOK LEV
:
the smoke level in supervisory mode. This level refers at
the
SMOKE
value (mod. Range:
80-150
). Beyond this
value, the alarm goes active.
NSUP.SMK LEV
:
the smoke level in no supervisory mode. This level refers
at the
SMOKE
value (mod. Range:
80-150
). Beyond this
value, the alarm goes active.
SMOKE(0-255)
:
it indicates the smoke into the detector with a range of
0-
255
(no mod.).
DIRTY %
:
the dirty % of the detector. If the value exceeds
80%
, the
control panel send the problem with a message (no mod.).
EFFICIENCY %
:
the efficiency % of the detector. If the value goes under
25%
, the control panel send the problem with a message.
This value depends of the device sensor (no mod.).
RATE-OF-RISE
:
if value is
YES
, the heat detector has rate-of-rise function
too (no mod.).
SUP.TEMP LEV
:
the temperature level in supervisory mode. This level
refers at the
TEMP.
value (mod. Range:
40-70
). Beyond
this value, the alarm goes active.
NSUP.TEMP LEV
:
the smoke level in no supervisory mode. This level refers
at the
TEMP.
value (mod. Range:
40-70
). Beyond this
value, the alarm goes active.
TEMP. °C
:
it indicates the temperature measure from the detector (no
mod.).
Point setting
•ADDRESS: 001-1
ZONE: 01
NAME: ROOM1
TYPE: SMOKE+HEAT DE
SECTION: A-B
OUT OF SERVICE: NO
FAULT: NO
LED ON: NO
INPUT: DISABLED
SINGLE CONSENSE: NO
SERIAL NUM:002-00001
SW VERSION: 2.00
SUPERV.SMOK LEV: 130
NSUPER.SMOK LEV: 100
SMOKE (0-255): 003
DIRTY %: 000
EFFICIENCY %: 100
RATE-OF-RISE: NO
SUPERV.TEMP LEV: 058
NSUPER.TEMP LEV: 056
TEMP. °C: 25.32
Esc. Pre. Next Mod.