Page 35 of 91
Rev. 4.20
7.1.6 Loop selection
Select the “
Loop
” to programme and confirm with “
Sel.
”, use the four
arrows to set oneself on the line that shows the loop the user wants to
programme and select and confirm with “
Sel.
”. Type in “
Canc
” to return to
the “
Point menu
”.
7.1.7 Point address selection
The control panel supplies the first free address to programme, relative to
the selected loop. Through the numerical keyboard it is possible to assign a
different number of address. Select “
Sel.
” to pass to the programming.
7.1.8 Detectors check values
The values assigned to the default detectors correspond to the current
norms (EN 54). However, for particular positions of the points, it is possible
to modify the levels of smoke and temperature alarm test, that the control
panel tests during the acquisition of a detector (it is not possible to modify
the levels of the single detectors). The control panel controls for every
detector that the value of smoke and temperature measured during the
acquisition step is comprised between the levels visualizes on the display.
Set yourself on the line and select “
Mod.
”. The data are modified with the
numerical keyboard. At the end of the possible modifications, confirm with
“
Ok
” to pass to the next menu.
7.1.9 Points Acquisition Modes: installer, activation and pre-set address
When the menu of point control values has been confirmed, the control
panel passes to the “
Information
” menu and begins the pre-selected
point research. The location procedure of the point depends on the selection
of the acquisition way.
The acquisition selection for “
INSTALLATION
” provides to insert the sensor
on the base.
The acquisition selection for “
ACTIVATION
” provides to press the micro
button of the modules or to get near with the magnet to activate the read of
the detectors.
The acquisition selection for “
PRESET ADDRESS
” provides to address the
points previously.
Press “
Canc
” to finish the search.
Loop selection
•LOOP 1
LOOP 2
LOOP 3
LOOP 4
Sel. Canc
Point addr. select.
ADDRESS: 001
Ok
.
Canc
Detect. checkvalues
•Min.TEMPERAT.°C: 015
Max.TEMPERAT.°C: 025
Min.SMOKE(0-255):000
Max.SMOKE(0-255):020
Ok
.
Mod. Del.
Information
•OPER.: POINT SEARCH
POINT: 001-1
Canc