ES 2050/51
Setting and changing of initial values
37
Alarm and warning relay outputs Input “Wait”
18. "Start" input
Regeneration delay 1
This time setting (0-999 seconds)
determines the number of
seconds the "Start" input is
blocked after a new regeneration
or a filter changeover, for instance to wait for a new analysis by a water
hardness meter.
See page 15, "Start" input.
NOTE: If the controller has been programmed for de carbonisation, this time is a delay as in
program step 18.2, but is activated only once after a regeneration or filter changeover, to allow the
water quality to be tested immediately using e.g. a pH meter.
Regeneration interruption 2
This time setting (0-999 seconds)
determines a delay period for the
"Start" input.
NOTE: If the "Wait" input is
selected in program step 17.1 for
the service cycle the delay time is not reset until a service valve is open and the
input is no longer active, i.e. no regeneration request if the operating valve is
open.
19. Service
You can determine whether a "SERVICE REQUIRED" message is shown on
the LCD display after a set supply quantity and whether the relay outputs
"warning" and/or "fault" are activated when this message is displayed.
NOTE: This program step can only be called up by the appropriate service
company.
You can set a service interval
from 1 to 650,000 m3.
The fault relay can be activated in
addition to the LCD display.
The report relay can be activated
in addition to the LCD display.
Step nr: 18.1
Reg. Delay 1 600s
Step nr: 18.2
Reg. Delay 2 10s
Step nr: 19.1
Maintenance Y/N
Step nr: 19.2
Interv. 50000m3
Step nr: 19.3
Alarm Y/N
Step nr: 19.4
Warning Y/N