ES 2050/51
Setting and changing of initial values
22
Time controlled regeneration
4. Time controlled regeneration
Regeneration can be initiated at fixed time intervals. This operating mode is
selected if a water meter is not desired either because the water usage is regular
and predictable or for operational reasons.
Sometimes this mode of operation is selected where there is a danger of micro
organism formation within the unit due to a prolonged standby period. The facility
is used to override volume dependant or quality dependant initiation.
At each time controlled regeneration, the water meter counter is reset.
A time period of between 1 to 999 hours between regeneration’s may be
programmed.
IMPORTANT! With installations utilising brine tanks it may be necessary to await
the availability of full strength brine, the actual time will depend upon the type of
brine system used but could exceed 4 hours.
Step nr: 4.1
Interim startY/N
Step nr: 4.2
Period 72h