15.Additional programme
(Regeneration-additional programme,
Flushing, High pressure pump).
The output "AD" (Additional Programme) can be used for the following functions:
Either:-
1.
AD = An additional programme
during regeneration. This allows
control of a valve or pump before, during or after a regeneration. It is
possible to program the output to operate for a time period of between 1
and 999 minutes. (Programme step 15.2-15.4)
or:-
2.
FL=A timed flush signal
which can be used to open a dump valve
flushing the plant to drain each time a pre-set volume of treated water
has been produced. It is possible to programme duration’s of between 1
and 255 seconds and volumes between successive flushes of between 1
and 65,000 litres (Programme step 15.5-15.6)
or:-
3.
HP=High pressure
pump allows control of a valve or pump during
the regeneration or service. The initiation will be controlled by the input
"WA".
IMPORTANT
See programme step 17 (Input "Wait").
Step nr: 15.1
Outp.AD:AD|FL|HP