ES 2050/51
Setting and changing of initial values
36
Alarm and warning relay outputs Input “Wait”
Refill chemical tank.
It can be determined whether the
operating valve of single filter
systems is to be closed or open in
the event of a fault.
Await regeneration.
17. Input “WAIT”.
The Input "WAIT" can be active either during the regeneration cycle or during
service.
During regeneration:
In duplex installations the stand
by unit comes into service if the
input is active during the start of
the regeneration. The initiation of the regeneration will be held off.
By pressing the "Start" button with the symbol
, the signal can be
overridden for the period of the regeneration.
By using the fast programme routine (see page 17) you can advance to the
next programme step.
Application: regeneration inhibition
During service:
The service valves will be opened and, if in programme step 15.1 HP (pump)
was selected, the output "AD" will operate.
Application: treated water storage tank level control.
Step nr: 16.8
Reg.tank low Y/N
Step nr: 16.9
SV open Y/N
Step nr: 16.10
Alarm Y/N
Step nr: 16.11
Warning Y/N
Step nr: 16.12
Wait Y/N
Step nr: 16.13
Alarm Y/N
Step nr: 16.14
Warning Y/N
Step nr: 17.1
Regener./Service