Profiles for PHOENIX MIG/MAG systems
Profiles for the CAN DeviceNet module
Item No.: 099-008225-EWM01
51
The data can only be assigned to a single connection in this profile.
Process data
Byte
no.
Bit no.
Function
Description
0
0
I > 0
Bit allocation:
0
1
"Current flows" signal from process
No current flowing
Current flows, arc stationary
0
1
Ready for welding
Bit allocation:
0
1
Ready signal from process
System not ready
System is ready
0 2 Sticking
Bit allocation:
0
1
Wire sticking message from process
Wire is free
Wire sticks to the workpiece
0 3 Error
Bit allocation:
0
1
General fault message from process
No error
Fault occurred and not rectified
0 4 Collision
signal
Bit allocation:
0
1
Signals triggering of the collision protection
No collision
Collision
0 5 Main
current
signal
Bit allocation:
0
1
Displays the status of the program sequence
Process is outside the main current phase
Process running in the main program
0 6 Process
active
Bit allocation
0
1
Signals the completion of the welding process
Process ended (after gas post-flows)
Process running
0 7 Reserved
1
0-7
Error
Error number of an error which has occurred
2 0-7
Monitoring
Bit allocation:
0
1
2
3
4-7
Bit field for displaying alarm messages during
welding parameter monitoring
Status = 0, no alarm
Status = 1, alarm
Welding voltage
Welding current
Wire feed speed
WF motor current
Reserved
3 0-7
User-defined
inputs
1 to 3 on bits 0 to 2
Input 3 is not available with
the seam tracking option
Signal status of the digital input
Logic:
0 V signal on the input = signal low
24 V on the input = signal high
4
0-7
Actual welding voltage value,
low byte
Current actual value for the welding voltage
Range: 0 to 0 x 7FFF
corresponds to 0.0 V to 100.0 V