Commissioning
Field bus connection and configuration
Item No.: 099-008225-EWM01
21
4.4.4.6 Baud rate
The module is equipped with automatic baud rate detection and therefore requires no additional setting
work.
The following baud rates are supported:
9.6kbit/s, 19.2kbit/s, 93.75kbit/s, 187.5kbit/s, 500kbit/s, 1.5Mbit/s, 3Mbit/s, 6Mbit/s, 12Mbit/s
4.4.4.7 Network termination
The Profibus network must be terminated on the line terminals to avoid signal reflections on the bus
medium. To do this, the module has an appropriate configuration switch:
Switch position
Setting
On
Bus termination is switched on.
Must be activated if the subscriber is on the first or last position and no
external termination is being used.
Off
Bus termination is switched off.
When using external termination (supported by various plugs, for example), the switch must be
switched to “Off”.
4.4.4.8 GSD file
The subscriber configuration is carried out via the GSD file supplied.
NOTE
For the remaining steps in the setup process, please refer to the "Special field bus
features when setting up the field bus modules" chapter.