44
10. MICRONOVA ELECTRONICS WITH LCD DISPLAY
10.3.11 Switching on the stove again
It will be possible to switch the stove back on only at the end of the safety period of time set by Pr38 and if the fume temperature
has reached a value below Pr13.
fig. 24
10.4 What happens in case of…
10.4.1 Pellet ignition failure
If pellets do not ignite, the display shows the alarm message “NO ACC” as shown in
figure 25
.
fig. 25
10.4.2 Power outage
Pr48 = 0
When the power is resumed after an outage, the stove enters the FINAL CLEANING phase and waits until the fume temperature
reaches a value below Pr13.
fig. 26
Pr48 = T seconds
After a power outage, one of the following conditions may occur depending on the stove previous status:
previous status
outage duration
new status
switched off
any
switched off
ignition
< T
ignition
pellet loading without pre-load
< T
pellet loading
pellet loading with pre-load
any
switching off
waiting for flame
< T
waiting for flame
working mode
< T
working mode
burn pot cleaning
< T
burn pot cleaning
switching off
< T
switching off
If the power outage duration is longer than T, the stove switches off.
room temperature
time clock
dialogue
heat output
Содержание MAJOLICA LINE
Страница 1: ...PELLET STOVES INSTRUCTION MANUAL MAJOLICA LINE SLIM LINE EN PELLET LINE...
Страница 3: ...2...
Страница 13: ...03 CANNA FUMARIA 12 EXISTING VENT PIPE TRADITIONAL EXTERNAL VENT PIPE...
Страница 22: ...21 07 INSTALLATION INSTRUCTIONS...
Страница 24: ...07 INSTALLATION INSTRUCTIONS 23...
Страница 25: ...08 DATA PLACES 24...
Страница 26: ...08 DATA PLACES 25...
Страница 27: ...08 DATA PLACES 26...
Страница 62: ...61 11 N100 MICRONOVA ELECTRONICS WITH 3 BUTTON LED DISPLAY 11 5 Connections...
Страница 70: ...69 12 N100 MICRONOVA ELECTRONICS WITH 6 BUTTON LED DISPLAY 12 5 Connections...
Страница 88: ...87...