Setting Ready delay to none zero causes ready to be set a fixed delay after the drive becoming ready. Ready is held high
until the drive is stooped by /Start, Program stop, Coast Stop or the drive becoming unhealthy. In the case of a /Start
command Ready will be low during the contactor delay period.
#
0RUH
#
1RWHV
=
•
Ready is independent of Enable.
•
The delay is only inserted for Start and not for JOG
$/$506
00,
#
(175,(6
......ALARMS / SEQ
........EXTERNAL TRIP [144] = FALSE
........MOTR.TMP.INHIBIT [146] = FALSE
f.......ACK ALARM [166] = TRUE
........STALL INHIBIT [143] = FALSE
........STALL TORQUE [136] = 95.00 %
........STALL SPEED [138] = 4.00 %
........STALL DELAY [137] = 10.00
........STALL TRIP [20] = OK
........OVER SPD INHIBIT [145] = FALSE
........OVER SPEED LEVEL [139] = 120.00 %
h.......UNDER V LEVEL [685] = 440 VOLTS
h......./UNDER VOLTS [686] = TRUE
........5703 RCV.INHIBIT [142] = FALSE
f.......SPD.FBK.DELAY [687] = 10.000 SECS
f.......SPD.FBK.THRESHD [688] = 10.00 %
........SPD.FBK.INHIBIT [689] = FALSE
h.......HEALTH INHIBIT [219] = 0x0000
f.......OPERATING MODE [25] = STOPPED
f.......DRIVE START [23] = FALSE
f.......DRIVE ENABLE [24] = FALSE
f.......READY [559] = FALSE
f.......RUN [28] = FALSE
f.......HEALTH STORE [203] = 0x0000
f.......HEALTH WORD [217] = 0x0000
f.......FIRST ALARM [218] = 0x0000
f.......HEALTHY [27] = TRUE
f.......HEALTH OUTPUT [12] = TRUE
#
$/$506
EXTERNAL TRIP
If set generates a user alarm / trip.
MOTOR.TMP.INHIBIT
Disables operation of the Motor Thermistor alarm
ACK ALARM
Must be TRUE to allow the automatic acknowledging of alarms by a start command
being reapplied.
By connecting this to a normally open digital i/p, the drive will wait for a LOW-
HIGH signal before restarting after a drive trip.
NOTE: 620L configurations from release 2.x set the value of ACK ALARM to
FALSE, requiring a low
→
high
→
low transition to acknowledge an active alarm.
67$//
STALL INHIBIT
Disables the stall alarm.
STALL TORQUE
The threshold at which torque must reach to be deemed as stalled.
STALL SPEED
The threshold for speed feedback below, which the stall condition is looked for.
Note the speed demand must also be above this threshold.
STALL DELAY
Time stall has to be present before if generates an alarm.
6WDOO
#
$OJRULWKP
IF ((|
SPEED_DEMAND|
>
STALL_SPEED
) AND (|
SPEED_FEEDBACK
| <
STALL_SPEED
) AND
|
TORQUE_DEMAND
| >
STALL_TORQUE
)) THEN Start Stall Timer
81'(5
#
92/7$*(
UNDER V LEVEL
(Engineering only) sets the level above which /.UNDER VOLTS is TRUE.
/UNDER VOLTS
(Engineering only) Under voltage signal, used to trigger saving of persistent data.