Value
Description
>0000
No error
>01C7
Invalid Mnemonic
>02C2
Checksum (BCC) error
>03C1
Line error, (parity, overrun or framing).
>04C8
Write only
>05C8
Read only
>07C8
Invalid Data (Encoding error)
>08C8
Data out of range
>0AC8
Tag initialisation error
>22CB
US control character expected
>23CB
RS control character expected
>24CB
GS control character expected
>25CB
FS control character expected
>26CB
Run Inhibit
>27CB
Configure Inhibit
>28CB
Tag is connected (unused)
Note: the 3dr digit “C” is used to denote a “Drive” instrument type. Older drives used to use an “F” in this location
to denote “Other” instrument type.
&200$1'
#2#
67$786
The following command / status parameters are supported:
Mnemonic
Description
Encoding
Range
Access
!1
Command
>XXXX
See Below
Write
Only
!2
State
>XXXX
See Below
Read Only
!3
Save Command
>XXXX
See Below
Write
Only
!4
Save State
>XXXX
See Below
Read Only
&200$1'
#+$4,
Command (!1) is a write only parameter used to modify the state of the 620 and to load configuration data from non-
volatile memory.
The following table lists the valid values for the request:
Value
Description
>1111
Restore Factory Defaults, P3 port only
>4444
Exit Re-Configuration Mode
>5555
Enter Re-Configuration Mode