S04, IP gateway
The address of the IP gateway is the address of the device which makes
it possible to access another network.
Factory setting:
192.009.200.254
IP gateway S04
192.009.200.254
In case of controlling via sACN you have to enter a really existing gateway or, by default, your
own IP address. Otherwise transmission of sACN data maybe faulty.
[EDIT]
takes you to the first numerical value. Select other numerical values by repeatedly
pressing the
[EDIT]
button.
S05, Dimmer count
Value range:
0
through
96
Factory setting:
72
Dimmer S05
count: 96
S06, DMX input failure
The behavior of the dimmer processor can be specified for the event that
the DMX input signal fail. Options are blackout, a preset or buffer input.
At timeout S06
blackout t=5s
The action is activated if the last input signals has failed. See the
M01
menu on page 8.
Open
•
Hit the
[ESC]
button until the main menu appears
•
Use
[PAGE]
or the encoder to scroll to the
M07
System
menu
•
[EDIT]
takes you to the most recently called system menu
Sxx
•
Use
[PAGE]
or the encoder to scroll to the
S06
At timeout
menu
Pressing the
[EDIT]
once offers you a selection of behavior options, pressing
[EDIT]
again offers the
corresponding buffer time.
Factory setting:
blackout t=5s
Blackout:
During the specified buffer time the most recently received
dimmer control level is maintained. Once this time has expired, all
dimmers are switched off.
Value range buffer time:
1s
through
99s
Factory setting buffer time:
5s
At timeout S06
blackout t=5s
Preset:
During the specified buffer time the most recently received
dimmer output level is maintained. Once this time has run out a locally
saved preset will be called up.
Value range presets:
1
through
24
Value range buffer time:
1s
through
99s
Factory setting buffer time:
5s
At timeout S06
preset 1 t=5s
Buffer input:
The most recently received dimmer output level is
maintained.
At timeout S06
buffer input
– 18 –
FDX2000 Vers. 4.0.0