Device Profile Area
CAN-CBX_Pt100
Manual • Doc.-No.: C.3032.21 / Rev. 1.1
Page 95 of 120
8.10.13 AI Interrupt Delta Input PV (9133
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
9133
h
0
Number_of_entries
4
4
unsigned 8
ro
1
AI_interrupt_delta_input_PV_1
80000000
h
...
7FFFFFFF
h
0
integer 32
rw
2
AI_interrupt_delta_input_PV_2
80000000
h
...
7FFFFFFF
h
0
integer 32
rw
3
AI_interrupt_delta_input_PV_3
80000000
h
...
7FFFFFFF
h
0
integer 32
rw
4
AI_interrupt_delta_input_PV_4
80000000
h
...
7FFFFFFF
h
0
integer 32
rw
Description of the parameter AI_interrupt_delta_input_PV_x (x = 1...4):
If a process variable is mapped on a PDO and the deviation of the process variable is higher than
specified in AI_interrupt_delta_input_PV_x, this PDO is transmitted.
The number of decimal places of the variable is defined in object “AI_decimal_digits_PV_x” (object
6132
h,
see page 91).
Value range:
AI_interrupt_delta_input_PV_x
Meaning
8000 0000
h
... FFFF FFFF
h
for negative values of the parameter a PDO-transmission is
initiated with every change of the process values
0
no comparison of the process values and thus no
transmission
0000 0001
h
.... 7FFF FFFF
h
a PDO-transmission will only be initiated, if the deviation
of the process values exceeds the value specified here.