Device Profile Area
Manual • Doc.-No.: C.3032.21 / Rev. 1.1
CAN-CBX_Pt100
Page 84 of 120
8.10.3 AI Sensor Type (6110
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
6110
h
0
number_of_entries
4
4
unsigned 8
ro
1
AI_sensor_type_1
1E
h
... 2732
h
2710
h
unsigned 16
rw
2
AI_sensor_type_2
1E
h
... 2732
h
2710
h
unsigned 16
rw
3
AI_sensor_type_3
1E
h
... 2732
h
2710
h
unsigned 16
rw
4
AI_sensor_type_4
1E
h
... 2732
h
2710
h
unsigned 16
rw
Description of the parameter AI_sensor_type_x (x = 1...4):
The parameter contains the type of the connected temperature sensor. The end number of the
variable name is the number of the measuring channel.
Value range:
Value of the parameters
Type of sensor resistor
30
(1E
h
)
Pt100 temperature sensor
31
Pt200 temperature sensor
32
Pt500 temperature sensor
33
Pt1000 temperature sensor
34
Pt5000 temperature sensor
10000
(2710
h
)
Resistance measurement
10030
Ni100 temperature sensor
10031
Ni200 temperature sensor
10032
Ni500 temperature sensor
10033
Ni1000 temperature sensor
10034
(2732
h
)
Ni5000 temperature sensor
Note:
When connecting temperature sensors, please note to set the type of the temperature sensor
in this parameter.
By default the parameter AI_sensor_type_x contains the value for resistance measurement
= 10000 (2710
h
).