Manufacturer Specific Profile Area
CAN-CBX_Pt100
Manual • Doc.-No.: C.3032.21 / Rev. 1.1
Page 105 of 120
8.11.8 Local Temperature at the Last Calibration (2421
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
2421
h
0
Number_of_entries
4
4
unsigned 8
ro
1
last_calibration_temp_1
8000
h
...7FFF
h
temp
_last_cal
_1
integer 16
ro
2
last_calibration_temp_2
8000
h
...7FFF
h
temp
_last_cal
_2
integer 16
ro
3
last_calibration_temp_3
8000
h
...7FFF
h
temp
_last_cal
_3
integer 16
ro
4
last_calibration_temp_4
8000
h
...7FFF
h
temp
_last_cal
_4
integer 16
ro
The default value temp
_last_cal
_x (x = 1 - 4) contains the temperature value which is measured at the last calibration.
Description of the variable last_calibration_temp_x:
This variable contains the value of the temperature on the circuit board in steps of 1/256
M
C,
determined at the last calibration of the corresponding channel.
The value is coded as described in the following:
Temperature C
Int
Value
d
[
]
_
°
=
16
256
Example:
last_calibration_temp_1 = 2640
h
=> Temperature = 38.25
M
C