PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
31
/
107
▲
and
▼
(see section 2.3).
Activate the
ENABLE-A
input (terminal 15),
ENABLE-B
input (terminal S) by releasing
the emergency button. Press the
START
button and the motor will start running. Make
sure that the motor is rotating in the correct direction. If not, set parameter
C014
(Phase Rotation) to [1:Yes], or open the
ENABLE-A,
ENABLE-B
and
START
inputs,
remove voltage from the drive and, after waiting at least 20 minutes, swap two of the
motor phases.
Press
STOP
to stop the motor. When the startup procedure is completed, set the drive
in remote mode by pressing
LOC/REM
. The L-CMD LED and L-REF LED will turn off.
6) Possible
failures:
If no failure occurred, go to step 7. Otherwise, check the drive connections paying
particular attention to supply voltages, DC link and input reference. Also check if alarm
messages are displayed. In the Measures Menu (section 2.5), check the reference
speed (
M001
), the supply voltage to the control section (
M030
), the DC link voltage
(
M029
), and the condition of control terminals (
M033
). Check to see if these readouts
match with the measured values.
7) Additional
parameter
modifications:
When parameter
P003
= Standby Only (condition required for changing C
parameters), you can change
Cxxx
parameters in the Configuration Menu only when
the drive is DISABLED or STOPPED, whereas if
P003
= Standby + Fluxing, you can
change
Cxxx
parameters when the motor is stopped but the drive is enabled.