PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
39
/
107
M032
Instant Digital Inputs
Range
Bit-controlled measure
See Table 1.
Active
Always active.
Address
1682
Function
Status of the virtual control terminal board before applying the timers to the digital inputs (if no timer is
applied, it matches with
M031
).
See
section 2.6.6.
Table 1: Coding of Measures M031, M032
Bit n.
Digital Input
Bit n.
Digital Input
0
MDI1
5
MDI6/ECHA/FINA
1
MDI2
6
MDI7/ECHB
2
MDI3(RESET)
7
MDI8/FINB
3
MDI4
8
ENABLE-SW
4
MDI5
9
ENABLE
M033
Local Control Terminal Board
Range
Bit-controlled measure
See Table 2.
Active
Always active.
Address
1683
Function
Status of the digital inputs in the drive physical terminal board.
The status of
MDI2&S (S)
input is the result of a logic AND between
ENABLE-A
and
ENABLE-B
physical signals.
Table 2: Coding of Measures M033
Bit n.
Digital Input
Bit n.
Digital Input
0
MDI1
4
MDI5
1
MDI2&S (S)
5
MDI6/ECHA/FINA
2
MDI3(RESET)
6
MDI7/ECHB
3
MDI4
7
MDI8/FINB
2.5.4.
Outputs Menu
This menu allows checking the status of the digital outputs, the analog outputs and the frequency outputs
located in the terminal board.
M056
Digital Outputs
Range
Bit-controlled measure
See Table 3
Active
Always active.
Address
1706
Function
Status of digital outputs MDO1
4 and status of the precharge contactor.
Table 3: Coding of Measure M056
Bit n°.
Digital Output
0
MDO1/FOUT
1
MDO2
2
MDO3
3
MDO4
6
Status of the precharge
contactor