If the PID regulator is adopted, parameter
P734
allows choosing whether to stop pipe fill when the preset fill
time is over, or even when the PID reference is attained.
When the PID is disabled, the Pipe Fill function will stop when the preset fill time is achieved and will be
resumed to reach the reference fill rate via the active ramps.
2.6.3.2. List of Parameters P730 to P734
Parameter
Function
User Level
Default Value
MODBUS
Address
P730
Pipe Fill Ramp
ADVANCED
10.0 s
932
P731
Pipe Fill Rate
ADVANCED
30.00%
933
P732
Pipe Fill Time
ADVANCED
5s
934
P734
Pipe Fill Enable Mode
ADVANCED
0: Disable
936
P730
Pipe Fill Ramp
Range
0 ÷ 32000
0 ÷ 3200.0 s
Default
100
10.0 s
Level
ADVANCED
Address
932
Function
Determines the time taken to go from zero rpm to the value set in
P731
.
P731
Pipe Fill Rate
Range
0 ÷ 32000
0 ÷ 320.00 %
Default
3000
30.00 %
Level
ADVANCED
Address
933
Function
Determines the pipe fill rate for the reference during the Pipe Fill stage.
P732
Pipe Fill Time
Range
0 ÷ 32000
0 ÷ 32000 s
Default
5
5 s
Level
ADVANCED
Address
934
Function
Indicates the time when the pipe fill rate is kept at the value set in
P731
.
P734
Pipe Fill Enable Mode
Range
0 ÷ 1
0: Disabled
1: Enabled
Default
0
0: Disabled
Level
ADVANCED
Address
936
Function
0: Disabled
The Pipe Fill function is inactive and the active ramps are implemented.
1: Enabled
The function is active; exiting the Pipe Fill mode is conditioned only when the preset times are over
2: E PID feedback
The function is active; exiting the Pipe Fill mode is conditioned when the preset times are over or
when the PID reference is attained.