SOLARDRIVE
PLUS
PROGRAMMING
GUIDE
22
/
107
W11 UPLOAD OK
If not, the
W12 UPLOAD KO
warning
appears.
Retry parameter upload.
While DOWNLOADING,
W07 DOWNLOADING (
flashing warning) appears.
If parameters are successfully downloaded, the following warning appears:
W09 DOWNLOAD OK
If not, alarm
A073
trips, and download must be retried before restarting the drive.
2.2.10.
LOC/REM Key
To enable the Local/Remote operating mode (Remote sources are command and/or reference sources other
than the display/keypad) press the
LOC/REM
key in the display/keypad, or use a digital input configured as
Loc/Rem
(see
C180
).
NOTE
The LOC/REM key is enabled when no digital input is configured as Loc/Rem, or when a digital
input is configured as a Loc/Rem button (see C180a).
The LOC/REM key is disabled when a digital input is configured as a Loc/Rem selector switch
(see C180a). For further information, please contact Enertronica Santerno.
C148
sets whether toggling between Remote mode and Local mode is activated only when the drive is
disabled, or whether toggling from Remote to Local mode does not affect the drive running conditions
(bumpless commands), but it does affect the reference. You can also choose to keep running conditions and
reference unaffected (any command is bumpless). For more details, please refer to the description of
parameter
C148
In LOCAL mode (the L-CMD and L-REF LEDs come on), when drive references and commands are sent via
display/keypad, the Keypad page allows changing the given reference using the
▲
and
▼
.
When not in LOCAL mode, press the
MENU
key to access the Keypad pages from the root page. Only the
Keypad pages relating to the Keypad source will be displayed along with the Measure Keypad page.
Example: Parameter
C147
(Torque Limit Reference Selection) is set to Keypad. From the root page, press
the
MENU
key once to display the Measure Keypad page, and press the
MENU
key twice to display the
Keypad page relating to the torque limit and allowing changing the torque limit reference using the
▲
and
▼
keys.
The Keypad page allows entering custom measures (see parameters
P268b
to
P268e
, contact Enertronica
Santerno).
From the Keypad pages, press the
SAVE/ENTER
key to access the Keypad Help page containing any details
about the measures displayed in the Keypad page.