PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
63
/
107
C018
Rated Motor Current
Range
1
32000
0.1
3200.0 A (Depending on the size)
Default
Depending on the size
Level
BASIC
Address
1018
Function
This parameter defines the rated motor current (nameplate rating).
C019
Rated Motor Voltage
Range
50
12000
5.0
1200.0 V
Default
4000
400.0 V
Level
BASIC
Address
1019
Function
This parameter defines the rated motor voltage (nameplate rating).
C020
Motor No-load Power
Range
0
1000
0.0
100.0%
Default
0
0.0%
Level
ADVANCED
Address
1020
Function
This parameter defines the power absorbed by the motor at rated voltage and rated rpm when no load
is connected to the motor.
C021
Motor no-load current
Range
1
100
1
100%
Default
0
0%
Level
ADVANCED
Address
1021
Function
This parameter defines the current absorbed by the motor at rated voltage and rated rpm when no
load is connected to the motor. It is expressed as a percentage of the motor rated current
C018
.
C022
Motor Stator Resistance
Range
0
32000
0.000
32.000
Default
Depending on the size
Level
ENGINEERING
Address
1022
Function
This parameter defines stator resistance Rs.
If a star connection is used, it matches with the value of the resistance of one phase (half the
resistance measured between two terminals); if a delta connection is used, it matches with 1/3 of the
resistance of one phase.
C023
Leakage Inductance
Range
0
32000
0.00
320.00mH
Default
Depending on the size
Level
ENGINEERING
Address
1023
Function
This parameter defines the global leakage inductance of the connected motor.
If a star connection is used, it matches with the value of the inductance of one phase; if a delta
connection is used, it matches with 1/3 of the inductance of one phase.