SOLARDRIVE
PLUS
PROGRAMMING
GUIDE
66
/
107
C035a
Frequency for Boost 0 Application
Range
0
99
0
99 %
Default
5
5%
Level
ADVANCED
Address
1052
Control
IFD
Function
Frequency for the application of the boost preset with parameter
C035
.
It is expressed as a percentage of the nominal motor frequency (
C015
).
C036
Voltage Boost 1 at Programmable Frequency
Range
–100
+400
–100
+400 %
Default
Depending on the size
Level
ADVANCED
Address
1036
Control
IFD
Function
Torque compensation at preset frequency (parameter
C037
). Determines how output voltage varies at
preset frequency with respect to voltage obtained with a constant V/f pattern (constant voltage
frequency). It is expressed as a percentage of the nominal motor frequency (
C019
).
C037
Frequency for Application of Voltage Boost 1
Range
6
99
6
99 %
Default
Depending on the size
Level
ADVANCED
Address
1037
Control
IFD
Function
Frequency for application of voltage Boost with parameter
C036
. This is expressed as a percentage of
the motor rated frequency (
C015
).
C038
Autoboost
Range
0
10
0
10 %
Default
Depending on the size
Level
ADVANCED
Address
1038
Control
IFD
Function
Variable torque compensation expressed as a percentage of the motor rated voltage. The preset
value expresses the voltage increase when the motor is running at its rated torque.
C039
Slip Compensation
Range
0
200
[0: Disabled]
200 %
Default
0
[0: Disabled]
Level
ADVANCED
Address
1039
Control
IFD
Function
This parameter represents the motor rated slip expressed as a value percent. If set to 0, this function
is disabled.