PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
49
/
107
P013
Deceleration Time at Stop 2
Range
0
32700
0
327.00 s if
P014
=0
0.01 s
0
3270.0 s if
P014
=1
0.1 s
0
32700 s if
P014
=2
1 s
0
327000 s if
P014
=3
10 s
Default
Depending on size
Level
ADVANCED
Address
613
Function
Same as ramp 1 (see
P010
).
NOTE
Values for ramp 2 can be applied to the reference provided that multiramp digital inputs are set up
and that ramp 2 is selected (for more details, contact Enertronica Santerno).
P014
Unit of Measure for Ramps 1 and 2
Range
0
3
0
0.01 s
1
0.1 s
2
1 s
3
10 s
Default
Depending on size
Level
ADVANCED
Address
614
Function
Defines the unit of measure for the time periods for speed ramp 1 (
P009
and
P010)
, for speed ramp 2
(
P012
and
P013
),
and for ramps in Fire Mode
(
P032
and
P033
). The allowable programmable range
may be extended from 0 s to 327000s.
E.g.
P014
=1 then
P009
=100; this means
P009
= 100 x 0.1 s = 10 s
P014
=0 then
P009
=100; this means
P009
= 100 x 0.01 s = 1 s
P014
=3 then
P009
=100; this means
P009
= 100 x 10 s = 1000 s
P015
Acceleration Time after Start
Range
0
32700
0
327.00 s if
P020
=0
0.01 s
Default
Depending on size
Level
ADVANCED
Address
615
Function
Ramp applied when the motor runs at constant speed and applied to the reference generated by the
algorithm for the Maximum Power Point Tracking (MPPT).
See also parameter
P009
(ramp for motor stop).