PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
79
/
107
C801
MDI Switch PV/AC Supply
Range
0
16
0
24 when ES847 or ES870 is
fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
5
5: MDI5
Level
ADVANCED
Address
753
Function
This parameter sets the digital input to the switch for DC or AC operation of the Solardrive Plus.
The programmed input is active if the switch is in DC position, while it is inactive if in AC position.
If your Solardrive Plus is not equipped with the DC/AC switch, the input is to be programmed
as 0
Inactive.
C802
Mains Loss Alarm Enabled
Range
0
1
0: No
1: Yes
Default
1
1: Yes
Level
ENGINEERING
Address
754
Function
Set
C802
= [1: Yes ] to enable
A064
Mains Loss alarm.
This parameter is helpful only if the equipment is provided with the DC/AC switch, and it takes effect
only when the switch is in AC position.
C803
MDI for PV Isolation Loss Detection
Range
0
16
0
24 when ES847 or ES870 is
fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
0: Disable
Level
ADVANCED
Address
1165
Function
This parameter sets the digital input allocated to isolation loss control. If the programmed input is
inactive, the drive operation is as described in parameter
C805
after the time set in parameter
C805
.
If your Solardrive Plus does not feature the isolation loss control functionality, set this
parameter to 0: Disable.
C804
Delay for PV Isolation Loss Detection
Range
0
32000
0
32000 ms
Default
0
0: Disable
Level
ADVANCED
Address
1306
Function
Delay associated with parameter
C803
.