Proline Prowirl 72
10 Technical data
E Hauser
61
Signal on alarm
• Current output: Failsafe mode can be selected (e.g. in accordance with NAMUR
Recommendation NE 43)
• Pulse output: Failsafe mode can be selected
• Status output: “not conductive” in event of fault
Load
A0001921
The area marked in gray indicates the permissible load (with HART: min. 250
Ω
)
The load is calculated as follows:
A0004059
R
B
Load, load resistance
U
S
Supply voltage:
- Non-Ex = 12...36 V DC
- Ex d = 15...36 V DC
- Ex i and Ex n = 12...30 V DC
U
Kl
Terminal voltage:
- Non-Ex = min. 12 V DC
- Ex d = min. 15 V DC
- Ex i and Ex n = min. 12 V DC
I
max
Output current (22.6 mA)
Low flow cut off
Switch points for low flow cut off can be selected as required
Galvanic isolation
The electrical connections are galvanically isolated from one another.
10.1.5
Power supply
Electrical connection
see Page 21 ff.
Supply voltage
Non-Ex: 12...36 V DC (with HART: 18...36 V DC)
Ex i and Ex n: 12...30 V DC (with HART 18...30 V DC)
EEx-d: 15...36 V DC (with HART: 21...36 V DC)
Cable entry
Power supply cable / signal cable (outputs):
• Cable entry: M20 x 1.5 (8...11.5 mm)
• Thread for cable entry: ½" NPT, G ½", G ½" Shimada
0
0
100
100
200
200
300
300
400
400
500
500
600
600
700
700
800
800
900
900
1000
1000
1100
1100
B
B
R
R
[ ]
[ ]
10
10
20
20
25
25
30
30
36
36
15
15
18
21
W
0
100
200
300
400
500
600
700
800
900
1000
1100
B
S
R
U
V
[ ]
[ ]
10
20
25
30
15
18
W
Ex i
Ex i und Ex n
W
Ex d
Ex
R
B
=
(U
S
Kl
– U )
(I
)
max
-3
– 10
0.022
=
(U
S
Kl
– U )
Содержание Proline Prowirl 72
Страница 4: ...QUICK SETUP for quick commissioning Proline Prowirl 72 4 Endress Hauser...
Страница 20: ...3 Installation Proline Prowirl 72 20 Endress Hauser...
Страница 42: ...6 Commissioning Proline Prowirl 72 42 Endress Hauser...
Страница 44: ...7 Maintenance Proline Prowirl 72 44 Endress Hauser...
Страница 114: ...www endress com worldwide BA084D 06 en 12 05 71008404 FM SGML 6 0...