11 Description of device functions
Proline Prowirl 72
102
E Hauser
11.2.14 Group SUPERVISION
Function description SUPERVISION
ACTUAL SYSTEM
CONDITION
The current system status appears on the display.
Display:
“SYSTEM OK” or the fault/notice message with the highest priority.
PREVIOUS SYSTEM
CONDITIONS
The last 16 fault and notice messages appear on the display.
ASSIGN SYSTEM ERROR
All system errors appear on the display. If you select a single system error you can change
its error category.
Display:
List of system errors
!
Note!
• Each individual message can be selected using the
O
and
S
key.
• If the
F
key is pressed twice, the ERROR CATEGORY function is called up.
• Use the
P
key combination or select “CANCEL” (in the system error list) to exit the
function.
ERROR CATEGORY
Use this function to define whether a system error triggers a notice message or a fault
message. If you select “FAULT MESSAGES”, all outputs respond to an error in
accordance with their defined failsafe mode.
Options:
NOTICE MESSAGES (display only)
FAULT MESSAGES (outputs and display)
!
Note!
• If the
F
key is pressed twice, the ASSIGN SYSTEM ERROR function is called up.
• Use the
P
key combination to exit the function.
ALARM DELAY
Use this function to define a time span for which the criteria for an error have to be
satisfied without interruption before a fault or notice message is generated. Depending on
the setting and the type of error, this suppression acts on the display, the current output
and the pulse/status output.
User input:
0...100 s (in steps of one second)
Factory setting:
0 s
"
Caution!
If this function is used, fault and notice messages are delayed by the time corresponding
to the setting before being forwarded to the higher-level controller (PCS, etc.). It is
therefore imperative to check in advance whether a delay of this nature could affect the
safety requirements of the process. If fault and notice messages may not be suppressed, a
value of 0 seconds must be entered here.
SYSTEM RESET
Use this function to reset the measuring system.
Options:
NO
RESTART SYSTEM
→
Restart without disconnecting main power
RESET DELIVERY
→
Restart without disconnecting main power, the saved settings of
the delivery status (factory settings) are applied.
Factory setting:
NO
Содержание Proline Prowirl 72
Страница 4: ...QUICK SETUP for quick commissioning Proline Prowirl 72 4 Endress Hauser...
Страница 20: ...3 Installation Proline Prowirl 72 20 Endress Hauser...
Страница 42: ...6 Commissioning Proline Prowirl 72 42 Endress Hauser...
Страница 44: ...7 Maintenance Proline Prowirl 72 44 Endress Hauser...
Страница 114: ...www endress com worldwide BA084D 06 en 12 05 71008404 FM SGML 6 0...