5 Operation
Proline Prowirl 72
38
E Hauser
5.4.5
Switching HART write protection on/off
A DIP switch on the amplifier board provides the means of activating or deactivating the HART
write protection. When the HART write protection is active, it is not possible to change the
parameters via the HART protocol.
1.
Unscrew the cover of the electronics compartment from the transmitter housing.
2.
Remove the display module (a) from the retaining rails (b) and refit onto right retaining rail with
the left side (this secures the display module).
3.
Fold up the plastic cover (c).
4.
Set the DIP switch to the desired position.
Position
A
, DIP switch at front = HART write protection disabled
Position
B
, DIP switch at rear = HART write protection enabled
!
Note!
The current status of the HART write protection is displayed in the WRITE PROTECTION
function (see Page 94).
5.
Installation is the reverse of the removal procedure.
A0001916
Fig. 24:
Switching HART write protection on/off
a
Local display module
b
Retaining rail for the display module
c
Plastic cover
A
HART write protection disabled (DIP switch at front)
B
HART write protection enabled (DIP switch at rear)
Esc
a
b
c
–
+
E
A
B
Содержание Proline Prowirl 72
Страница 4: ...QUICK SETUP for quick commissioning Proline Prowirl 72 4 Endress Hauser...
Страница 20: ...3 Installation Proline Prowirl 72 20 Endress Hauser...
Страница 42: ...6 Commissioning Proline Prowirl 72 42 Endress Hauser...
Страница 44: ...7 Maintenance Proline Prowirl 72 44 Endress Hauser...
Страница 114: ...www endress com worldwide BA084D 06 en 12 05 71008404 FM SGML 6 0...