Picomag IO-Link
Commissioning
Hauser
25
Unidirectional flow measurement (Q), conductivity measurement (S)
A = 0
B
Q
mA
20
16
12
8
4
A0035753
A
Lower range value = 0
B
Upper range value
Q
Flow
• Current I is linearly interpolated between lower range value (A) and upper range value
(B).
• The output range ends at 20.5 mA.
Bidirectional flow measurement (Q), temperature measurement (T)
A = 0
B
Q
mA
20
16
12
8
4
A0035754
A
Lower range value
B
Upper range value
Q
Flow
• Current I is linearly interpolated between lower range value (A) and upper range value
(B).
• Rather than having a hard upper and lower limit, the output range ends at 20.5 mA at
the top end and at 3.8 mA at the bottom end
Configuring the pulse output
The Pulse output submenu contains all the parameters that must be configured for the
configuration of the pulse output.
Navigation
Menu: "Guidance" → Output 1
Parameter overview with brief description
Parameter
Description
User entry
Factory setting
Value per pulse
Enter the value for the pulse output.
Floating point number with sign
Depends on the nominal diameter:
DN 15 (½"): 0.5 ml
DN 20 (¾"): 1.0 ml
DN 25 (1"): 2.0 ml
DN 50 (2"): 10.0 ml