Picomag IO-Link
Commissioning
Hauser
27
Switch on if over the limit:
Switch off if over the limit:
1
0
A
B
t
C
1.1
1.2
Q / T
A0034163
1.1 Input variables
1.2 Switch output
A
Switch-on point
B
Switch-off point
C
Hysteresis
Q / T
1
0
A
B
t
C
2.1
2.2
A0034164
2.1 Input variables
2.2 Switch output
A
Switch-on point
B
Switch-off point
C
Hysteresis
Switch on if within window:
Switch off if within window:
Q / T
1
0
A
t
D
D
3.1
3.2
B
B
A
A0034165
3.1 Input variables
3.2 Switch output
A
On-value (lower range limit)
B
Off-value (upper range limit)
D
Window
Q / T
1
0
A
B
t
D
D
4.1
4.2
A
B
A0034166
4.1 Input variables
4.2 Switch output
A
On-value (lower range limit)
B
Off-value (upper range limit)
D
Window
Configuring the voltage output
The Voltage output submenu contains all the parameters that must be configured for the
configuration of the voltage output.
Navigation
Menu: "Guidance" → Output 1
Menu: "Guidance" → Output 2
Parameter overview with brief description
Parameter
Description
Selection/input
Factory setting
Assign voltage output
Select process variable for voltage output.
• Off
• Volume flow
• Temperature
• Conductivity
Volume flow
2 V value
Enter the lower range value.
Floating point number with sign
0 l/min
10 V value
Enter the upper range value.
Floating point number with sign
Depends on the nominal diameter:
DN 15 (½"): 25 l/min
DN 20 (¾"): 50 l/min
DN 25 (1"): 100 l/min
DN 50 (2"): 750 l/min