Commissioning
Picomag IO-Link
28
Hauser
Unidirectional flow measurement (Q), conductivity measurement
A = 0
B
Q
V
10
8
6
4
2
A0032995
A
Lower range value = 0
B
Upper range value
Q
Flow
• Voltage U is linearly interpolated between lower range value (A) and upper range value
(B).
• The output range ends at 10.25 V.
Bidirectional flow measurement (Q), temperature measurement (T)
0
B
Q
V
10
8
4
2
A
6
A0032996
A
Lower range value
B
Upper range value
Q
Flow
• Voltage U is linearly interpolated between lower range value (A) and upper range value
(B).
• Rather than having a hard upper and lower limit, the output range ends at 10.25 V at
the top end and at 1.9 V at the bottom end
Configuring the digital input
The
Digital input
submenu contains all the parameters that must be configured for the
configuration of the digital input.
The input is used to control an action with an external voltage signal. The minimum pulse
duration is 100 ms.
Navigation
Menu: "Guidance" → Output 1