14.2 IO-Link process data
14.2.1 Data structure
Bit
number
119…
112
111…
104
103…
96
95…
88
87…
80
79…
72
71…
64
63…
56
55…
48
47…
40
39…
32
31…
24
23…
16
15…
8
7…0
Data
Conductivity in µS/cm
Totalizer in l
Volume flow in l/s
Temperature
in ¹⁄₁₀ °C
Status
Data
type
32-bit floating point
number with single
precision (IEEE 754)
32-bit floating point
number with single
precision (IEEE 754)
32-bit floating point
number with single
precision (IEEE 754)
16-bit two's
complement
8-bit
Data structure of the status bits 7 to 0
Bit
Description
0
Switches once per sampling rate
1
Reserved
2
Current status S-Out 1
3
Current status S-Out 2
4
Reserved
5
Reserved
6
Reserved
7
Reserved
14.2.2 Diagnostic information
Diagnostic code
Display text
Coding
(hex)
PDValid
Validity
Priority
Status
NE 107
Diagnostic number
–
SYSTEM OK
0x0000
1
1
F
181
COIL CIRC.FAIL.
0x5000
0
2
F
180
TEMP.CIRC.FAIL.
0x5000
0
3
F
201
DECICE FAIL.
0x5000
0
4
F
283
MEMORY FAIL.
0x8C00
0
5
C
446
I/O 1 OVERLOAD
0x180C
1
6
C
447
I/O 2 OVERLOAD
0x180C
1
7
C
485
SIMULATION ACT.
0x8C01
1
8
C
453
FLOW OVERRIDE
0x180D
1
9
S
441
I-OUT 1 RANGE
0x180A
1
10
S
444
U-OUT 1 RANGE
0x1809
1
11
S
443
P-OUT 1 RANGE
0x180B
1
12
S
442
I-OUT 2 RANGE
0x180A
1
13
S
445
U-OUT 2 RANGE
0x1809
1
14
S
962
EMPTY PIPE
0x180E
1
15
S
834
TEMPERAT. RANGE
0x8C20
1
16