Operation
Memocheck Sim CYP03D
34
Hauser
Path: Menu/Advanc. function
Function
Configuration options
(factory settings in bold)
Error simulation
Leak. curr. alarm
Leak. curr. warn
Temp. sens. defect
Sensor supply
Once you have selected an error using ,
the error is output at the transmitter. To
delete the error again, remove the check
mark again using .
Ramp
Ramp
(continuous)
Ramp (gradual)
Sim. main value
Starting
value
Stop value
Duration
Number of
steps
Time per step
Conc. liquid
-0.02 to
120.0 mg/l
-0.02 mg/l
-0.02 to
120.0 mg/l
120.0 mg/l
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Current
0.0 pA to
640.0 nA
0.0 nA
0.0 pA to
640.0 nA
640.0 nA
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Saturation
-0.02 to
1000 % sat
-0.02 % sat
-0.02 to
1000 % sat
1000 % sat
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Partial pressure
0.0 to 440.0
hPa
0.0 hPa
0.0 to 440.0
hPa
440.0 hPa
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Conc. gas.
0.0 to
100.0 %
0.0 %
0.0 to
100.0 %
100.0 %
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Temperature
-40.0 to 60.0
˚C
-40.0 °C
-40.0 to 60.0
˚C
60.0 °C
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Salinity
0.0 to 40.0
g/kg
0.0 g/kg
0.0 to 40.0
g/kg
40.0 g/kg
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Process pressure
500 to 9999
hPa
500 hPa
500 to 9999
hPa
9999 hPa
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Altitude
-300 to 4000
m
-300 m
-300 to 4000
m
4000 m
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Raw value current
0.0 pA to
640.0 nA
0.0 pA
0.0 pA to
640.0 nA
640.0 nA
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Raw value temp.
-40.0 to 60.0
˚C
-40.0 °C
-40.0 to 60.0
˚C
60.0 °C
10 to 6000 s
60 s
1 to 200
10
0.5 to 600 s
1 s
Содержание Memocheck Sim CYP03D
Страница 2: ...Declaration of Conformity Memocheck Sim CYP03D 2 Endress Hauser Declaration of Conformity ...
Страница 51: ......