11. Troubleshooting Tips
The
motor
will
not run.
The
inverter
outputs
U,V and
W are not
supplying
voltage.
Inverter
outputs
U,V,W are
supplying
voltage.
Symptom/condition
Probable Cause
Countermeasure
¡
Is power being supplied to
terminals L1, L2
If so, the power lamp should
be on.
¡
Is there an error code
E
¡¡
displayed?
¡
Check terminals L1, L2
then U, V, and W
¡
Turn on the power supply
or check fuses.
¡
Are the signals to the intelli-
gent input terminals correct?
¡
Is the Run Command active?
¡
Is the[FW] terminal (or [RV]
connected to CM1(via switch,
etc.)
¡
Has the frequency setting
for F01 been set greater than
zero?
¡
Are the control circuit term-
inals H, O, and L connected
to the potentiometer?
¡
Is the motor load too heavy?
¡
Is the motor locked?
¡
Reduce load, and test the
motor independently.
¡
Is the RS(reset) function
or FRS(free-run stop)
function on?
¡
Turn off the command(s)
¡
Set the parameter for F01
to a safe, non-zero value.
¡
If the potentiometer is the
frequency setting surce,
verify voltage at"O"
£
0V
¡
Verify the terminal functions
for C01-C06 are correct.
¡
Turn on Run Command
¡
Supply 24V to [FW] or [RV]
terminal, if configured.
(Terminal mode selection)
¡
Press the Func key and
determine the error type.
Then clear the error(Reset).
¡
Is the frequency command
source A01 parameter setting
correct?
¡
Is the Run command source
A02
correct?
parameter setting
¡
Make sure the parameter
A01
setting correct?
¡
Make sure the parameter
A02
setting correct?
11-1
ENDA E-100
INSTRUCTION MANUAL