Overload Restriction
b06
b07
b08
3
150.0%
0.1sec
Overload
restriction
level setting
Overload
restriction
constant setting
Overload
overvoltage
restriction
mode selection
Select overload or overvoltage restriction
modes
0.... Overload, overvoltage restriction mode
OFF
1.... Only overload restriction mode ON
2.... Only overvoltage restriction mode ON
3.... Overload overvoltage restriction
mode ON
Sets the level for overload restriction,
between 20% and 200% of the rated
current of the inverter, setting range- 0.2
¡
( inverter rated current)
¡
2.0
¡
( inverter
rated current).
¡
¡
¡
Set the deceleration rate when inverter
detects overload,
range is 0.1 to 10.0 and
resolution is 0.1
b07
b08
Motor
Current
Output
frequency
b04
b05
100.0%
1
Electronic
thermal
characteristic,
selection
Electronic
thermal
level setting
Set a level between 20% and 120% for
the rated inverter current.
setting range- 0.2
¡
(inverter rated
current)
¡
1.2
¡
(inverter rated current).
¡
¡
Electronic Thermal Overload Alarm Setting
Select from two curves, option codes:
0....(SUB) reduced torque characteristic
1....(CRT) constant torque characteristic
100
80
60
0
5
20
60
120
Constant torque(CRT)
Reduced torque(SUB)
Output frequency(Hz)
output
current
Func-
code
Name
Description
Defaults
Run-
time
Edit
Func-
code
Name
Description
Defaults
9-16
ENDA E-100
INSTRUCTION MANUAL