General Specifications
The following table applies to all E-100
inverters.
Item
General Specifications
Frequency setting
resolution
Protective housing *1
Enclosed type(IP20)
Space vector PWM control
Digital command : ¡0.01% of the maximum frequency
Analog command : ¡0.1% of the maximum frequency
Digital : 0.01Hz(100Hz and less), 0.1Hz
(100Hz or more)
Analog : Max. Setting frequency / 500(DC 5V input),
max. setting frequency / 1000(DC 10V, 4
¡
20mA)
0.01 to 400Hz
Control method *6
Output frequency range *4
Frequency accuracy
Overload current rating
Acceleration/deceleration
time
Operator panel
Operator panel
Potentiometer
External signal
External signal
Intelligent input
terminal
Volt./ Freq. Characteristic
Freq-
setting
FWD/
REV
Run
In
p
u
t
si
g
n
al
Any base freguency setting possible between 0Hz
and 400Hz.
V/F control (constant torque, reduced torque).
150%, 60 seconds
0.1 to 3000sec., (linear accel. / decel. s-curve,
u-curve), second accel. / decel. setting available
Up and Down keys / Value settings
Analog setting via potentiometer.
1W, 1§ to 2 variable resistor
DC 0¡5V, DC 0¡10V(Input Impedonce 700§)
4¡20mA(Input Impedonce 25§)
§
Run/Stop(Forward/Reverse run change by command)
Forward run/stop, Reverse run/stop set by terminal
assignment (NC/NO)
FW(forward run command), RV(reverse run
command), CF1
¡
CF4(multistage speed setting),
JG(jog command), 2CH(2-stage accel./decel.
command), FRS(free run stop command),
EXT(external trip), USP (unattended startup),
SFT(soft lock), AT(analog current input select
signal), RS(reset), SET(2nd setting selection)
3-2
ENDA E-100 INSTRUCTION MANUAL