A40
A41
0.00Hz
¡
Jump(hysteresis)
frequency width
setting
Defines the distance from the center
frequency at which the jump around
occurs. Range is 0.00 to 10.00Hz in
units of 0.01Hz
A41
A43
A45
PID Control(Note1)
A46
A47
A48
A49
0
10.0%
10.0sec
0.0sec
¡
Proportional gain has a range of 0.1
to 100 in units of 0.1.
PID P
(proportional)
gain setting
PID I (integral)
gain setting
PID D(deriva-
tive) gain setting
PID Function
selection
Integral time constant has a range of
0.0 to 100.0 seconds in units of 0.1
Enables PID function, two option codes:
0.... PID control disable
1.... PID control enable
Derivative gain has a range of 0.0 to
100 .0 seconds in units of 0.1
Automatic Voltage Regulation (AVR) Function
A52
A53
0
220V
¡
¡
200V class inverter settings:
.... 200/220/230/240
400V class inverter settings:
.... 380/400/415/440/460
Motor input
voltage setting
AVR function
selection
Automatic (output) voltage regulation,
selects from three type of AVR funct-
ions, three option codes:
0... Constant ON
1... Constant OFF
2... OFF during deceleration
A50
A51
100
1
¡
¡
PID scale factor
setting
Feed-back
method setting
PID scale factor (multiplier),
range of 0.1 to 1000 in units of 0.1
Selects source of PID, option codes:
0.... "OI" terminal(current in put)
1.... "O" terminal(voltage in put)
Func-
code
Name
Description
Defaults
Run-
time
Edit
¡
¡
¡
9-11
ENDA E-100
INSTRUCTION MANUAL