2CH FW
Output
frequency
Time
[FW, RV]
[2CH]
Two-stage Acceleration and Deceleration[2CH]
¡When terminal [2CH] is turned on, the
inverter changes the rate of acceleration
and deceleration from the initial settings
(acceleration time1) and
(deceleration time1) to use the second
set of acceleration / deceleration values.
¡When the terminal is turned off, the
equipment is turned off, the equipment is
returned to the original acceleration and deceleration time
( acceleration time1 and deceleration time1). Use
(acceleration time2) and (deceleration time2) to set the second
stage acceleration and deceleration time.
¡In the graph shown above, the [2CH] becomes active during the initial
acceleration. This causes the inverter to switch form using acceleration 1
( ) to acceleration 2 ( )
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
7
2CH
Two-stage
Acceleration
and Deceleration
ON
OFF
Frequency output uses 2nd-stage
acceleration and deceleration values
Frequency output uses the initial
acceleration 1 and deceleration 1
values
Valid for inputs
Required setting
C01,C02,C03,C04,C05
A54, A55, A56
Notes:
¡
Function A56 selects the method for
second stage acceleration. It must be
00 to select the input terminal method
in order for the 2CH terminal
assignment to operate.
Example:
8-10
ENDA E-100
INSTRUCTION MANUAL