Remark
1. If satisfactory performance through auto-tuning cannot be fully obtained,
please adjust the motor constants for the observed symptoms according to the
table below.
2. If the inverter capacity is more than twice the capacity of the motor in use,
the inverter may not achieve its full performance specifications.
3. Running multiple motor under sensorless vector control is not available.
4. When DC braking is enabled, the motor constant will not be accurately set.
Therefore, disable DC braking before starting the auto-tuning procedure.
5. The motor will rotate up to 80% of base frequency : make sure that accele-
ration or deceleration is not operated. If then, decrease the manual torque
boost setting value.
6. Be sure if motor is in standstill before you carry out an auto-tuning.
Auto-tuning data carried out when motor is still running may be not correct.
7. If the auto-tuning procedure is interrupted by the stop command, the auto-
tuning constants may be stored in the inverter. It will be necessary to store
the inverters factory defaults setting.
Powered
running
(status with a
accelerating
torque)
When low frequency
(a few Hz) torque is
insufficient.
H06/H11
Slowly increase the motor constant
R1 in relation to auto-tuning data
within 1 to 1.2 times R1.
Slowly increase the motor constant
R1 in relation to auto-tuning data
within 1 to 1.2 times R1.
Slowly increase the motor constant
R2 in relation to auto-tuning data
within 1 to 1.2 times R2.
Slowly increase the motor constant
IO in relation to auto-tuning data
within 1 to 1.2 times IO.
Slowly increase the motor constant
IO in relation to auto-tuning data
within 1 to 1.2 times IO.
Slowly decrease the motor constant
R2 in relation to auto-tuning data
within 0.8 to 1 times R2.
Decrease the carrier frequency.
Regeneration
(status with a
decelerating
torque)
When low frequency
(a few Hz) torque
is insufficient.
When over current
prote ction is operated
at injection of load
When the speed
deviation is positive
When the speed
deviation is negative.
H07/H12
H07/H12
H10/H15
H06/H11
H10/H15
b11
Operation
status
Symptom
Adjustment
Parameter
8-28
ENDA E-100
INSTRUCTION MANUAL